Display
Hex
configured measured value
source
B_012
0C
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_015
0F
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_016
10
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_017
11
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_018
12
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_031
1F
Output, totalizer output
B_060
3C
Output
Only if the failure behavior of the analog input function block is set to "The incorrectly
1)
calculated measured value is on output".
Only if the failure behavior of the totalizer function block has been set to "Operation".
2)
See also
Error display (Page 74)
Status display (Page 76)
Status (Page 167)
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
PDM display
Cause
Bad,
Device has an irrepa-
rable error
Device error
Bad,
Device has an irrepa-
rable error
Device error, value
constant
Bad,
Sensor indicates an
error.
Sensor error
Bad,
Negative pressure too
high. Low control limit
Sensor error, limit
violated (<-20% of
value violated
nominal measurement
range).
Bad,
Positive pressure too
high. High control limit
Sensor error, limit
violated (>120% of
value violated
nominal measurement
range).
Bad,
Function block was
placed out of service
Out of service, value
with a target mode
constant
command. A parame-
terized safety value is
output.
Bad;
Device is not yet in
safe state.
configuration error
Interrupts, error and system alarms
12.1 Overview of status codes
Measure
Replace the electronics.
Replace the electronics.
Have a service technician
check the sensor.
Increase the pressure in
the positive direction.
Reduce the pressure.
For normal operation,
reset the target mode to
AUTO.
Complete PROFIsafe
commissioning.
191