Operation
6.5 Local operation
Condition for "setting"
You are familiar with the correct operation of the pressure transmitter and the associated
safety information.
Setting electrical damping
To set electrical damping to 0 seconds, proceed as follows:
1. Set mode 4.
2. Press the [↑] and [↓] buttons simultaneously.
3. Save with the [M] button.
Result
Electrical damping has been set to 0 seconds.
Condition for "adjusting"
The default adjusting of steps is an interval of 0.1 seconds. If you press the [↑] or [↓] button
for a long time, the steps are increased.
Adjusting electrical damping
To adjust electrical damping, proceed as follows:
1. Set mode 4.
2. Adjust the desired damping.
3. Save with the [M] button.
Result
Electrical damping has been set to the desired time constant.
See also
Operation using buttons (Page 79)
Electrical damping (filter time constant) (Page 116)
6.5.4

Calibrate zero point

Introduction
A zero point calibration is used to correct zero errors resulting from the mounting position of
the transmitter. You must proceed differently depending on the device version.
80