Functional safety
8.7 PROFIsafe
Device modes
Display
A specific Generic Station Description (GSD) file is assigned to each device mode:
Display
8.7.9.2

Configuration with host system

Note
Generic Station Description (GSD)
The generic station description file in HW Config remains the same: SI0180A6.gsd.
162
Meaning
[0]: Profile-compliant:
Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0, with analog input
function block (without totalizer) (as standard device only)
[1]: State as shipped
Profile-compliant with expansions:
Full range of functions of the SITRANS P, series DS III PROFIsafe with:
Analog input function block
Safe analog input
Totalizer
PROFIsafe communication in mode V1 or V2 possible
[2]: Can be replaced by the predecessor device SITRANS P, series DS III PA (only as stand-
ard device)
[128]: Profile-compliant:
Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0 (as standard de-
vice only)
Analog input function block
Totalizer
[129]: •
Can be replaced by SITRANS P, series DS III PROFIsafe with PROFIsafe communica-
tion only possible in V1 mode.
In this device operating mode a SITRANS P, DS III PA series (standard device with
Profibus Profile 3.00 or 3.01) can be replaced by a SITRANS P, DS III PROFIsafe se-
ries (firmware version 0301.02.03 or higher).
File name
[0]: pa_29700.gsd or pa_39700.gsd
[1]: siem8170.gsd
[2]: sip1804B.gsd
[128]: pa_29740.gsd or pa_39740.gsd
[129]: SI0180A6.gsd or SIEM80A6.gsd or SI0280A6.gsd
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08