Functional safety
8.7 PROFIsafe
8.7.7.1
Activate and parameterize PROFIsafe with SIMATIC PDM
Procedure
1. Click the "Upload to PC" button.
SIMATIC PDM reads in the parameters from the device.
2. Under ">> PROFIsafe", set the "PROFIsafe activation" parameter to "Yes".
3. Set the "F_Dest_ADD" parameter so that it has the same value as in HW Config.
4. If you must change other parameters, then parameterize them.
5. Press the "Download to device" button.
Result
The device has activated the PROFIsafe functionality. The relevant menus for PROFIsafe
commissioning are active in SIMATIC PDM.
Note
If you want to change the "F_Dest_ADD" parameter later, reset the device.
Resetting the device (Page 159)