Interrupts, error and system alarms
12.1 Overview of status codes
Display
Hex
configured measured value
source
U_072
48
Totalizer output
U_075
4B
Output, totalizer output
U_079
4F
Output, totalizer output
U_080
50
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put, totalizer output
U_081
51
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put, totalizer output
U_082
52
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put, totalizer output
B_000
00
Output (cyclical data only),
totalizer output (cyclical
data only)
B_004
04
Raw pressure value, sec-
ondary variable 1, second-
ary variable 2, measured
value (primary variable),
secondary variable 3, out-
put 1), totalizer output 2)
B_011
0B
Secondary variable 3
190
PDM display
Cause
Unsure,
Use of the totalizer
block if the measured
Replacement value
value status is "Bad"
and the parameterized
safety setting is "Safe
operation". The
summed value chang-
es. Failure behavior =
safe operation.
Unsure,
Value is not an auto-
matic measurement
Replacement value,
value. A parameteriza-
value constant
ble, static replacement
value or preset value is
marked in this manner.
Unsure,
An initial value is writ-
ten to the device
Initial value, value
memory after startup.
constant
Unsure,
Impermissible operat-
ing parameter or ser-
Value inexact
vice alarm.
Unsure,
Low nominal range
measurement limit
Value inexact, limit
violated (<0%).
value violated
Unsure,
High nominal range
measurement limit
Value inexact, limit
violated (>100%).
value violated
Bad
Used if no other infor-
mation is available.
Device does not exist
or cyclical connection
is interrupted.
Bad,
Calibration span too
small.
Configuration error
Bad,
Variable is not calcu-
lated
not connected, value
constant
Measure
Check the data meas-
urement.
Check the data meas-
urement.
Throw away the value in
the application program.
Check the operating
parameters, e.g. the
permissible ambient
temperature. Immediate
service required.
Increase the pressure in
the positive direction.
Reduce the pressure.
-
Repeat the calibration
procedure with pressure
values which are farther
apart.
Correct the "transmitter
type" setting.
SITRANS P DS III/P410 with PROFIBUS PA