Checking A Device With Add-On Remote Seal; Profisafe; Introduction; Technical Advantages Of Profisafe - Siemens SITRANS P DS III Operating Instructions Manual

Digital pressure transmitter
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

3. Check the following valves for correct positioning and absence of leaks:
– Process valves
– Stabilizing valve
– Vent valves
– Blowout valves or plugs
4. Observe the safety information and specifications in chapter Commissioning (Page 171).
8.6.2

Checking a device with add-on remote seal

Procedure
1. Check the connection between the pressure transmitter and remote seal and between the
remote seal and the plant for leaks.
2. Observe the safety information and specifications in chapter Installing / mounting
(Page 39).
8.7

PROFIsafe

8.7.1

Introduction

PROFIsafe enables safe communication by detecting and reporting all communication
errors. Data security is continuously monitored on the PROFIBUS in the process.
8.7.2

Technical advantages of PROFIsafe

The main advantage of PROFIsafe is that the PROFIBUS communication channel becomes
secured by a protocol in a transparent way. Thus incorrect values cannot be transferred to
the master without being discovered. The user does not need any special network
components. All the user needs is the standard network components of PROFIBUS.
However, the CPU must be suitable for safety applications.
In the following example, you see that PROFIsafe and PROFIBUS devices can be operated
simultaneously on a PROFIBUS network.
Note
PROFIsafe devices can only be operated with the S7 F Systems V6.1 configuration software
in combination with S7-400H.
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Functional safety
8.7 PROFIsafe
141

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans p410

Table of Contents