Operation
6.5 Local operation
Table 6- 4
Operating functions using buttons
Function
Measured value
Error display
Electrical damping
Zero point calibration
(position correction)
Locking of buttons and
functions
Measured value dis-
play
Unit
Bus address
Operating mode of
device,
see also Device opera-
tion type (Page 88)
Decimal point
Zero point adjustment
LO calibration
HI calibration
78
Mode
Button function
[M]
[↑]
[↓]
Here you
can se-
lect the
modes.
4
Increase
De-
damping
creased
damping
7
Increase
Decrease
1)
correction
correc-
value
tion value
10
Change
13
Select from various
possibilities.
14
Select from table for
measured value
display.
15
Increase
Decrease
16
Change
17
To left
To right
18
19
Increase
Decrease
value
value
20
Increase
Decrease
value
value
Display, explanations
[↑] and [↓]
The current measured value is displayed as
you have set it in the function "Measured-
value display, mode 13".
Error
Set to 0
Time constant T
Range of adjustment: 0.0 s to 100.0 s
Apply
Pressurize the pressure transmitter for gauge
pressure, differential pressure, flow rate or
level.
Evacuate pressure transmitter for absolute
pressure (< 0.1 ‰ of the measuring span).
Measured value in pressure unit
Cancel 5 s *)
L
LC
LA
LL
*) Does not apply to "Safe (PROFIsafe)
mode". In this case, refer to the information in
section "PROFIsafe (Page 141)".
Selection of various variables
First value in
Physical unit
each case
from the phys-
ical unit table
Node address on the PROFIBUS
Value between 0 and 126
Selection of operating mode of device
Profile-compatible 1 AI
Profile-compatible with extensions
Old SITRANS P/PA device
Profile-compatible 1 AI, 1 TOT
Position of decimal point in display
Display of current measuring range
Apply
Calibrate bottom point of characteristic
Apply
Calibrate top point of characteristic
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
A fault exists.
in seconds
63
Locking of buttons and functions
(hardware write protection); local
operation disabled
Write blocking; local operation pos-
sible
Enabling of local operation
Combination of write blocking and
no enabling of local operation

Advertisement