3.7.3.4

Measuring cell for absolute pressure from the differential pressure series

Image 3-8
● Absolute pressure is transmitted to the absolute pressure sensor
diaphragm
● When measuring limits are exceeded, the overload diaphragm
seal diaphragm
protects the absolute pressure sensor
● The difference between the inlet pressure (p
negative side of the measuring cell displaces the seal diaphragm
changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure
sensor.
● The change in the resistance causes a bridge output voltage proportional to the absolute
pressure.
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Pressure cap
Seal diaphragm on the measuring cell
O-ring
Measuring cell body
Absolute pressure sensor
Function chart of measuring cell for absolute pressure
and the filling liquid
rests on the measuring cell body
Overload diaphragm
Measuring cell filling liquid
Reference pressure
p
Pressure input variable
e
.
. The seal diaphragm thus
from overload.
) and the reference pressure
e
Description
3.7 Principle of operation
through the seal
is displaced until the
on the
. The displacement
33