Display
[2]
[128]
Procedure
To change the device mode, proceed as follows:
1. Set mode 16.
The current operation type "0", "1", "2" or "128" appears in the measured value display.
2. Select the device mode.
The local operation type must match the operation type in PROFIBUS.
3. Save with the [M] button.
Note
Each device operation type is assigned a particular device master data file (GSD file).
If the configuration of your PROFIBUS-PA strand does not correspond to the device
mode selected, the device will not start periodic data exchange. Successful establishment
of communication is identified by the indicator "o" at the top left of the display.
Note
If the device is exchanging period data, no change is possible to the device operating
type.
Table 6- 18
Display
[0]
[1]
[2]
[128]
See also
Errors (Page 192)
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Meaning
Exchangeable for previous SITRANS P/PA device
Profile-compliant:
Exchangeable for pressure transmitter with PROFIBUS PA Profile 3.0 with:
Analog input function block
•
Totalizer.
•
Device master data file
File name
pa_29700.gsd or pa_39700.gsd
siem80A6.gsd
sip1804B.gsd
pa_29740.gsd or pa_39740.gsd
Operation
6.5 Local operation
89