Process
Import EDD with SIMATIC PDM (Page 145)
Configure CPU with HW Config (Page 145)
Configure device with HW Config (Page 145)
Configure CFC (Page 148)
8.7.5.1
Import EDD with SIMATIC PDM
To import the EDD, click on "SIMATIC PDM" > "Manage Device Catalog".
8.7.5.2
Configure CPU with HW Config
The relevant settings for fail-safe of the CPU are located in the CPU-specific documentation.
Procedure
If your CPU is a SIMATIC CPU, proceed as follows:
1. Double click on the CPU.
2. You are now in the "Properties" dialog box on the "Protection" tab. Activate the following
checkboxes:
– Protection level "1"
– "Removable with password"
– "CPU contains safety program"
8.7.5.3
Configure device with HW Config
Procedure
1. You are in the "Catalog" view with the "standard" profile. Go to the device in the catalog:
– "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe"
– "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe
2. Pull the following device onto "PA Master System" with Drag & Drop.
The "Properties" dialog then opens.
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
valid for firmware 0301.02.01 and 0301.02.02
V2"
valid as of firmware 0301.02.03
Note
You will find the valid firmware version on the label and can then select the correct
GSD file for your version.
Functional safety
8.7 PROFIsafe
145