Flow Measurement - Siemens SITRANS P DS III Operating Instructions Manual

Digital pressure transmitter
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

● Create an assignment between the measured mass value and the output value by setting
these parameters:
>
>
>
>
You can also adjust the output to another process value. Assign the required unit to the
parameters under the rubric output scaling. Assign the start of scale and full scale values
according to the measured value scaling.
See also
Adjusting to a desired process value (Page 114)
7.4.5

Flow measurement

● Select the required configuration with the configuration tool:
Table 7- 6
Desired configuration
Output
Totalizer output
Output, totalizer output
Output, totalizer output, reset totalizer output
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Output
>
Function block 1 - analog input
Channel:
>
>
Measured value scaling
Start of scale value:
Full scale value:
>
>
Output scaling
Unit:
Start of scale value:
Full scale value:
Desired configuration for flow measurement
Operator control functions via PROFIBUS
Measured value (primary variable)
as in "working range"
as in "working range"
Unit of mass [kg, g, t ...]
as "measured value scaling" * density
as "measured value scaling" * density
Measurement type
Current flow/time
Volume or mass that has flowed over a time
segment
Current flow/time,
volume or mass that has flowed over a time seg-
ment,
reset totalizer output (with SIMATIC PDM)
Current flow/time,
volume or mass that has flowed over a time seg-
ment,
Dosing
7.4 Settings