Measurement Setup - Flow - Siemens SITRANS L Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Figure 4.8
Foam generation
Through the action of filling, stirring and other processes in the vessel, foams which
considerably damp the emitted signals may form on the medium surface.
If foams lead to measurement errors, you should use transmitters with guided radar.
4.4

Measurement setup - Flow

In general, the following must be observed while mounting the device:
Detailed project planning data can be found at the channel manufacturers and in the
technical literature.
The following examples serve as an overview for flow measurement.
SITRANS LR110
Operating Instructions, 12/2020, A5E49829013
Agitators
Mounting the transmitter on the upstream or inlet side
Installation in the centre of the flume and vertical to the liquid surface
Distance to the overfall orifice or Venturi flume
Min. distance to the max. height of damming for optimum accuracy: 250 mm
1
(9.843 in)
1
At smaller distances the measuring accuracy is reduced, see "Technical data".
Installing/mounting
4.4 Measurement setup - Flow
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr110

Table of Contents