Flow Measurement

SITRANS F C
Transmitter MASS 6000 IP67 compact/remote
Technical specifications
Measurement of
Current output
Current
Load
Time constant
3
Digital output
Frequency
Time constant
Active
Passive
Relay
Type
Load
Functions
Digital input
Functionality
Galvanic isolation
Cut-off
Low-flow
Limit function
Totalizer
Display
Zero point adjustment
Ambient temperature
Operation
Storage
Communication
3/206
Siemens FI 01 · 2018
© Siemens AG 2018
Mass flow [kg/s (lb/min)],
volume flow [l/s (gpm)],
fraction [%],
3
3
°Brix, density [kg/m
, (lb/ft
)],
temperature [°C (°F)]
0 ... 20 mA or 4 ... 20 mA
< 800 Ω
0 ... 99.9 s adjustable
0 ... 10 kHz, 50 % duty cycle
0 ... 99.9 s adjustable
24 V DC, 30 mA,
1 KΩ ≤ R
≤ 10 KΩ,
load
short-circuit-protected
3 ... 30 V DC, max. 110 mA,
250 Ω ≤ R
≤ 10 KΩ
load
Change-over relay
42 V/2 A peak
Error level, error number, limit,
flow direction
11 ... 30 V DC (R
= 13.6 kΩ)
i
Start/hold/continue batch, zero
point adjust, reset totalizer 1/2,
force output, freeze output
All inputs and outputs are galva-
nically isolated.
Isolation voltage:
• 500 V to supply
• 50 V between outputs
0 ... 9.9 % of maximum flow
Mass flow, volume flow, fraction,
density, sensor temperature
Two eight-digit counters for for-
ward, net or reverse flow
• Background illumination with
alphanumerical text, 3 × 20
characters to indicate flow rate,
totalized values, settings and
faults. Time constant as current
output 1
• Reverse flow indicated by nega-
tive sign
Via keypad or remote via digital
input
-20 ... +50 °C (-4 ... +122 °F),
max. rel. humidity 80 % at 31 °C
(87.8 °F) decreasing to 50 % at
40 °C (104 °F) according to
IEC/EN/UL 61010-1
-40 ... +70 °C (-40 ... +158 °F)
(Humidity max. 95 %)
Add-on modules: HART,
PROFIBUS PA and DP,
Modbus RTU RS 485,
DeviceNet,
FOUNDATION Fieldbus H1
Update 08/2018
Enclosure
Material
Rating
Mechanical load
Supply voltage
24 V version
• Supply
230 V version
• Supply
Power consumption
24 V DC
24 V AC
230 V AC
Fuse
230 V version
24 V version
EMC performance
Emission
Immunity
NAMUR
Environment
Environmental conditions acc. to
IEC/EN/UL 61010-1:
Maintenance
Cable glands
Note
Due to RoHs directives active from July 22
transmitters of any model and variants are not for sale within EU,
EU candidate countries, Norway, Switzerland, Iceland, Croatia,
and Turkey.
Replacement products: 7ME461.-..., 7ME462.-..., 7ME471.-...
and 7ME481.-...
Repair parts for MASS 6000 (all models and variants) are avail-
able. See spare part list.
Fibre glass reinforced polyamide
IP67/NEMA 6
18 ... 1000 Hz random,
3.17 g RMS, in all directions
18 ... 30 V DC
20 ... 30 V AC
87 ... 253 V AC, 50 ... 60 Hz
6 W
10 VA
9 VA
T 400 mA, T 250 V (IEC 127) - not
replaceable by operator
T 1 A, T 250 V (IEC 127) - not
replaceable by operator
EN 55011/CISPR-11 (Class A)
EN/IEC 61326-1 (Industry)
Within the value limits according
to "General requirements" with
error criteria A in accordance with
NE 21
• Altitude up to 2000 m
• POLLUTION DEGREE 2
The flowmeter has a built-in error
log/pending menu which should
be inspected on a regular basis.
Two types of cable gland are
available in polyamide in the fol-
lowing dimensions:
M20 or ½" NPT