Table 5-1 Causes Of Errors For Pos_Err - Siemens simatic et 200s Operating Instructions Manual

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

Feedback Messages
Address
Assignment
Byte 0
Bit 7: ERR_ENCODER
Bit 3: SYNC
Bit 2: POS_ DONE
Bit 1: POS_ERR
Bit 0: POS_ACK
Byte 4
Bit 7: ERR_2L+
Bit 1: JOB_ERR
Bit 0: JOB_ACK
Causes of Errors for POS_ERR
Table 5-1
Causes of Errors for POS_ERR
Error Number
Cause
1
MODE unknown
2
ERR_2L+ is displayed
3
ERR_ENCODER is displayed
4
The axis is not synchronized (SYNC=0)
5
The limit switch that lies in the direction in which
the drive is moved is active
7
Inching: DIR_P and DIR_M = 1
Absolute positioning:
Start with DIR_P and DIR_M = 0 or relevant
control bit DIR_P or DIR_M = 0
Relative positioning:
Start with DIR_P and DIR_M = 0 or DIR_P and
DIR_M = 1
8
Absolute positioning: Destination ≥ encoder range
13
Direction of rotation of the drive and the encoder
varies
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
5.6 Functions of the 1PosSSI/Digital
Remedy
Permissible MODEs are:
MODE 0
MODE 1
MODE 3
MODE 4
MODE 5
Check the load voltage (2L+) at terminal 15
Check the encoder wiring
Eliminate the encoder error.
Check your switches and the wiring as well as the
DI0 limit switch minus and DI1 limit switch plus
parameters
Check the wiring of the drive and the encoder as
well as the reversal of the direction of rotation
parameter
1PosSSI/Digital