1PosUniversal/Digital
7.6 Functions of the 1PosU
7.6.18

Error Detection/Diagnostics

Parameter assignment error
Parameter assignment error
Causes:
The 1PosU cannot identify existing parameters as its
own.
The slot of the 1PosU you have configured does not
match the setup.
Only at SSI encoder:
Impermissible value for parameter for number of
increments.
Impermissible value for parameter for number of
rotations.
Number of increments * number of rotations is
greater than 4096x4096.
Only at SSI encoder:
Activated "Encoder signal" diagnostics
Activated "Reversal of the direction of rotation"
What to Do:
Check the configuration and setup
360
Response of the 1PosU
The 1PosU is not assigned parameters and cannot execute
its functions.
Generate channel-specific diagnostics
Operating Instructions, 05/2007, A5E00124871-04