Advertisement

6.6.20

Error Detection/Diagnostics

Parameter assignment error
Parameter assignment error
Causes:
The 1PosSSI/Analog cannot identify existing
parameters as its own.
The slot of the 1PosSSI/Analog you have configured
does not match the setup.
Impermissible value for parameter for number of
increments.
Impermissible value for parameter for number of
rotations.
Number of increments * number of rotations is
greater than 4096x4096.
What to Do:
Check the configuration, physical setup and
parameter assignment.
External Errors
Short circuit of the sensor supply
Causes:
Short circuit of the encoder supply made available at
terminals 2 and 10
What to Do:
Check the wiring and correct the short circuit.
Acknowledge the error with the EXTF_ACK control
bit.
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
6.6 Functions of the 1PosSSI/Analog
Response of the 1PosSSI/Analog
The 1PosSSI/Analog is not assigned parameters and cannot
execute its functions.
Generate channel-specific diagnostics
Response of the 1PosSSI/Analog
The current MODEs relative positioning and absolute
positioning are stopped; it is not possible to start a new run
in these MODEs.
Analog output QV+ is set to 0 V
Digital output OUT:
If the direction is assigned parameters for the DO
function, the digital output OUT=0 is set
Feedback bit POS_ERR = 1
Feedback bit POS_DONE = 0
Feedback bit ERR_ENCODER=1
Feedback bit SYNC = 0
Generate channel-specific diagnostics
Waits for error acknowledgment EXTF_ACK
Inching MODE is not affected by this error.
1PosSSI/Analog
291