Siemens simatic et 200s Operating Instructions Manual page 330

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

1PosUniversal/Digital
7.6 Functions of the 1PosU
Control Signals: Inching
Address
Byte 0
Feedback Signals: Inching
Address
Byte 0
Bytes 1 to 3
Inching: Causes of Errors for POS_ERR
You must find out the causes of errors with JOB 15 (displays current values).
Error Number
2
5
7
13
15
330
Assignment
Bits 0.7 to 0.4:
Bit
7
6
0
0
Bit 3: SPEED (SPEED = 0 is creep feed; SPEED = 1 is rapid feed)
Bit 2: DIR_M
Bit 1: DIR_P
Bit 0: START
Assignment
Bit 2: POS_ DONE
Bit 1: POS_ERR
Bit 0: POS_ACK
Actual value
at incremental encoder (linear axis: 0 to 16 777 215; rotary axis: 0 to end of rotary
axis-1)
at SSI encoder (0 to encoder range - 1)
Cause
ERR_2L+ is displayed
The limit switch that lies in the
direction in which the drive is
moved is active
Inching: DIR_P and DIR_M = 1
Direction of rotation of the drive
and the encoder varies
In dosing operation DIR_M = 1
5
4
MODE 1 = Inching
0
1
What to Do
Check the load voltage (2L+) at terminal 7
Check your switches and the wiring as well as
the DI0 limit switch minus and DI1 limit switch
plus parameters
Check the wiring of the drive and the encoder
as well as the reversal of the direction of
rotation parameter
Operating Instructions, 05/2007, A5E00124871-04