Changing the Voltage for Rapid Feed (JOB 5)

Definition
By changing the voltage for rapid feed (JOB 5) you can adjust the speed for rapid feed.
Supply the control interface with the new rapid feed voltage and activate JOB 5.
You can set a voltage between 0 V and 11.7589 V (including overrange) in S7 analog value
format (you will find a detailed explanation in the
The 1PosInc/Analog accepts the preset voltage. When the drive runs in rapid feed, it
accelerates/decelerates at the set acceleration/deceleration rate to the new rapid feed
voltage. The voltage remains valid until the parameter assignment of the 1PosInc/Analog is
changed.
Effect on the MODEs
MODE
Search for Reference
Inching
Absolute Positioning
Relative Positioning
Control Signals: Changing the Voltage for Rapid Feed
Address
Byte 4
Bytes 5 to 7
Feedback Signals: Voltage for rapid feed
Address
Byte 4
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
What Happens
When the drive runs in rapid feed, it accelerates/decelerates at the set
acceleration/deceleration rate to the new rapid feed voltage.
-
When the drive runs in rapid feed, it accelerates/decelerates at the set
acceleration/deceleration rate to the new rapid feed voltage.
Assignment
Bits 4.7 to 4.4 :
Bit
7
6
0
1
Bit 0: JOB_REQ
Voltage for rapid feed
0 to 32 511 in S7 analog value format
Assignment
Bit 1: JOB_ERR
Bit 0: JOB_ACK
4.6 Functions of the 1PosInc/Analog
Distributed I/O Device
5
4
JOB 5 = Change the voltage for rapid
0
1
feed
1PosInc/Analog
manual).