Terminal Assignment Diagram - Siemens simatic et 200s Operating Instructions Manual

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

3.3

Terminal Assignment Diagram

Wiring rules
The wires to the incremental encoder (terminals 1 and 5, 3 and 7 and 4 and 8) have to be in
twisted pairs and shielded. The shield must be supported at both ends. You use the shield
contact element (Order Number: 6ES7 390-5AA00-0AA0) as a shield support.
Terminal assignment
The following figure shows you the terminal assignment for the 1PosInc/Digital:
Terminal assignment
Connection of Relays and Contactors to the Digital Outputs
Note
Direct connection of inductivities (such as relays and contactors) is possible without external
circuiting.
If SIMATIC output circuits can be deactivated by additionally installed contacts (for example
relay contacts), you have to provide additional overvoltage protection devices at inductivities
(see the following example for overvoltage protection).
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
View
Connection of the Incremental
Encoder with 5 V Differential
Signals: Terminals 1-8
1: A
5: /A
3: B
7: /B
2: DC24
6: M
4: N
8: /N
3.3 Terminal Assignment Diagram
Remarks
Connection of the Switches and the
Drive: Terminals 9-16
Track A
9: IN0
13: IN1
Track B
14: IN2
10: DC24
Voltage supply for
11: OUT0
incremental encoder
12: OUT1
Track N; optional
16: OUT2
zero mark
15: 2L+
1PosInc/Digital
Minus limit switch
Plus limit switch
Reducing cam;
latch signal
Encoder supply for
the switches
Travel minus or
rapid feed
Travel plus or creep
feed
Rapid/creep feed
and travel
plus/minus
Load voltage infeed
for OUT0, OUT1
and OUT2
59