Errors When Transferring The Data Record - Siemens SIMATIC ET 200SP Manual

Analog input module ai 8xrtd/tc 2-wire hf 6es7134-6es7134-6jf00-0ca1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

A.3

Errors when transferring the data record

Error transferring the data record
The module always checks all values of the data record to be sent. The module applies the
values from the data record only when all values have been transmitted without errors.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter, see also the description of the "STATUS" parameter
in the STEP 7 online help).
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Manual, 09/2018, A5E32942580-AB
Meaning
Byte 3
xx
Number of the data record
unknown.
xx
Length of the data record
incorrect.
xx
Slot invalid or cannot be
accessed.
xx
Wrong version or error in the
header information.
xx
Parameter error
A.3 Errors when transferring the data record
Solution
Enter a valid number for the data record.
Enter a valid value for the data record length.
Check the station to determine whether the
module is plugged or pulled.
Check the assigned values for the parameters
of the WRREC instruction.
Correct the version, length and number of parame-
ter blocks.
Check the parameters of the module.
Parameter data record
65

Advertisement

Table of Contents
loading

Table of Contents