Installation, Wiring, and Fitting
Install and wire the TM-E30S44-01 terminal module. Insert the 1PosSSI/Digital in the
terminal module (you can find detailed instructions in the
Terminal assignment
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
5.2 Brief Introduction to Commissioning the 1PosSSI/Digital
View
Connection of the SSI Encoder:
Terminals 1-8
1: D
5: /D
3: B
7: /B
2: 24 V DC
6: M
4: C
8:/C
Distributed I/O Device
Remarks
Connection of the Switches and the
Drive: Terminals 9-16
9: IN0
Data from the SSI
13: IN1
encoder
14: IN2
Unused terminals
10: 24 VDC
11: OUT0
Power supply for
SSI encoder
12: OUT1
16: OUT2
SSI clock (clock
line)
15: 2L+
1PosSSI/Digital
manual).
Minus limit switch
Plus limit switch
Latch signal
Encoder supply for
the switches
Travel minus or rapid
feed
Travel plus or creep
feed
Rapid/creep feed and
travel plus/minus
Load voltage infeed
for OUT0, OUT1 and
OUT2
191