Installation, Wiring, and Fitting
Install and wire the TM-E30S44-01 terminal module. Insert the 1PosSSI/Analog in the
terminal module (you can find detailed instructions in the
Table 6-1
Terminal assignment of the 1PosSSI/Analog
Terminal assignment
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
6.2 Brief Instructions on Commissioning the 1PosSSI/Analog
View
Connection of the SSI Encoder:
Terminals 1-8
1: D
5: /D
3: B
7: /B
2: 24 V DC
6: M
4: C
8:/C
Distributed I/O Device
Remarks
Connection of the Switches and the
Drive: Terminals 9-16
Data from the SSI
9: IN0
encoder
13: IN1
Unused terminals
14: IN2
10: 24 VDC
Power supply for
12: QV+
SSI encoder
16: M
SSI clock (clock
11: OUT
line)
15: M
1PosSSI/Analog
manual).
Minus limit switch
Plus limit switch
Reducing cam; latch
signal
Encoder supply for the
switches
Analog output ± 10 or
0 V to 10 V to connect
ana
the drive
Digital output for direct
control or as a
directional signal for
the drive