Terminal Assignment Diagram; Table 4-2 Terminal Assignment Of The 1Posinc/Analog - Siemens simatic et 200s Operating Instructions Manual

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

1PosInc/Analog

4.3 Terminal Assignment Diagram

4.3
Terminal Assignment Diagram
Wiring rules
The wires to the incremental encoder (terminals 1 and 5, 3 and 7 and 4 and 8) have to be in
twisted pairs and shielded. The shield must be supported at both ends. You use the shield
contact element (Order Number: 6ES7 390-5AA00-0AA0) as a shield support.
Terminal assignment
Table 4-2
Terminal assignment of the 1PosInc/Analog
Terminal assignment
Connection of Relays and Contactors to the Digital Output
Note
Direct connection of inductivities (such as relays and contactors) is possible without external
circuiting.
If SIMATIC output circuits can be deactivated by additionally installed contacts (for example
relay contacts), you have to provide additional overvoltage protection devices at inductivities
(see the following example for overvoltage protection).
120
View
Connection of the Incremental
Encoder with 5 V Differential
Signals: Terminals 1-8
1: A
5: /A
3: B
7: /B
2: 24 VDC
6: M
4: N
8:/N
Remarks
Connection of the Switches and the
Drive: Terminals 9-16
Track A
9: IN0
13: IN1
Track B
14: IN2
10: 24 VDC
Voltage supply for
12: QV+
incremental
16: M
encoder
Track N; optional
11: OUT
zero mark
15: M
Operating Instructions, 05/2007, A5E00124871-04
Minus limit switch
Plus limit switch
Reducing cam; latch
signal
Encoder supply for
the switches
Analog output ± 10 or
0 V to 10 V to connect
ana
the drive
Digital output DO for
direct control or as a
directional signal for
the drive
ET 200S Positioning

Advertisement

Table of Contents
loading

Table of Contents