Inching: Causes of Errors for POS_ERR
You must find out the causes of errors with JOB 15 (displays current values).
Error Number
5
7
13
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
Assignment
Bits 0.7 to 0.4:
Bit
7
0
Bit 2: DIR_M
Bit 1: DIR_P
Bit 0: START
Voltage for inching
(0 to 32 511)
Assignment
Bit 2: POS_ DONE
Bit 1: POS_ERR
Bit 0: POS_ACK
Actual value
(0 to encoder range - 1)
Cause
The limit switch that lies in the direction in which
the drive is moved is active
Inching: DIR_P and DIR_M = 1
Direction of rotation of the drive and the
encoder varies
Voltage for inching >32 511 or < 0
6
5
4
MODE 1 = Inching
0
0
1
What to Do
Check your switches and the wiring as well as
the DI0 limit switch minus and DI1 limit switch
plus parameters
Check the wiring of the drive and the encoder
as well as the parameter for the reversal of the
direction of rotation and adapting the direction
of the drive.