Technical Data of the 1PosInc/Analog
Data on the Digital Output
Output voltage
Output current
Switch rate
Lamp load
Output delay (resistive load, output current 0.5 A)
Short-circuit protection of the output
Threshold on
Inductive extinction
Digital input control
Cable lengths
Data for the Analog Output
Resolution (including overrange)
Settling time
Length of cable
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
Rated value
0 signal
1 signal
0 signal (leakage current)
1 signal
Rated value
Permitted range
Resistive load
Inductive load
Lamp load
At 0 to 1
At 1 to 0
Unshielded
Shielded
For resistive load
For capacitive load
For inductive load
Shielded
4.10 Technical Specifications for the 1PosInc/Analog
24 VDC
≤ 3 V
≥ L+ -1 V
≤ 0.3 mA
0.5 A
7 mA to 0.6 A
100 Hz
2 Hz
≤ 10 Hz
≤5 W
typ. 150 µs
typ. 150 µs
Yes
0.7 A to 1.8 A
Yes; L+ -(55 to 60 V)
Yes
600 m
1000 m
± 10 V/13 bits + sign
0,1 ms
0.5 ms
0.5 ms
Max. 100 m
1PosInc/Analog
185