Siemens simatic et 200s Operating Instructions Manual page 370

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

1PosUniversal/Digital
7.8 Parameter List
Parameter List at Incremental Encoders with 24 V Signals
Parameters
Enables
Group diagnostics
Encoder signal
diagnostics
Axis
Dosing operation
Sensor
Reversal of the
direction of rotation
Axis type
End of rotary axis
Digital Inputs
DI0 limit switch minus
DI1 limit switch plus
DI2 reducing cam
Reference point run and evaluation of the reference signal
Reference signal
Reference switch
Start direction of the
reference point run
370
Meaning
When group diagnostics is enabled, an
encoder error (ERR_ENCODER), no load
voltage (ERR_2L+) or a parameter
assignment error will result in a channel-
specific diagnostics.
A simultaneous edge change at Signals A
and B causes an error.
Only the encoder signal A is evaluated.
This means that only a path change in the
positive direction is possible.
Selection of the output circuit of the
encoder for the signals A, B and N
Adjustment of the direction of rotation of the
encoder A reversal of the direction of
rotation is only possible if no dosing
operation is set.
Selection of linear axis without limits or
rotary axis with overrun/underrun with
encoder range
Only relevant for rotary axis type:
Underrun: 0 to end of rotary axis - 1
End of rotary axis - 1 to 0
Switch on the DI0 digital input is a break or
make contact
Switch on the DI1 digital input is a break or
make contact
Switch on the DI2 digital input is a break or
make contact
This parameter defines the relevant switch
or the combination of switch and zero mark.
Relevant in the case of reference signal:
Reference switch and zero mark
Reference switch
This parameter defines the referencing
direction in which the switch must be
traversed.
Value range
Disable
Enable
On
Off
Off
On
Current-sourcing
switch, push-pull
Mono-switch
Off
On
Linear
Rotary
1 - 16 777 215
Break contact
Make contact
Break contact
Make contact
Break contact
Make contact
Reference switch and
zero mark
Reference switch
Zero mark
Reduction cam towards
minus
Reduction cam towards
plus
Minus limit switch
Plus limit switch
Plus
Minus
Operating Instructions, 05/2007, A5E00124871-04
Default setting
Disable
On
Off
Current-sourcing
switch, push-pull
Off
Linear
36 000
Break contact
Break contact
Make contact
Reference switch and
zero mark
Reduction cam
towards minus
Plus
ET 200S Positioning