Siemens simatic et 200s Operating Instructions Manual page 336

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

1PosUniversal/Digital
7.6 Functions of the 1PosU
Example 3: Reference Point Run with Reversal of Direction at the Plus Limit Switch
● Start position: between the minus limit switch and the reducing cam
● Start direction: Plus
● Reference signal: Reference switch and zero mark
● Reference switch: Reduction cam towards plus
Figure 7-13
If the start position is at the plus limit switch, the 1PosInc/Digital controls directly the drive in
rapid feed in the opposite direction to the assigned parameter start direction.
Example 4: Reference Point Run Only with Zero Mark
● Start position: between the minus limit switch and the plus limit switch
● Start direction: Minus
● Reference signal: Zero mark
● Reference switch: irrelevant
Figure 7-14
336
Reference Point Run with Reversal of Direction at the Plus Limit Switch
Reference Point Run Only with Zero Mark
Operating Instructions, 05/2007, A5E00124871-04
ET 200S Positioning

Advertisement

Table of Contents
loading

Table of Contents