Cpu/Master Stop And Reset State - Siemens simatic et 200s Operating Instructions Manual

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

5.7

CPU/Master Stop and RESET State

Behavior at CPU-Master-STOP
Behavior at CPU-Master-STOP
Due to power-off of the CPU/DP master
or
Due to power-off of the IM 151/ IM 151 FO
or
Due to failure of DP transmission
or
Due to change from RUN to STOP
Exiting the CPU-Master-STOP Status
Exiting the CPU-Master-STOP Status
At power-on of the CPU/DP master
or
At power-on of the IM 151/ IM 151 FO
or
After failure of the DP transmission
or
After a change from STOP to RUN
RESET State of the 1PosSSI/Digital
RESET Status of the 1PosSSI/Digital and Modification
of the Parameters of the 1PosSSI/Digital
By changing the parameters of the 1PosSSI/Digital
and downloading the parameter assignment and
configuration of the ET 200S station to the CPU/ DP
master
or
As a result of power-on of the power module of the
1PosSSI/Digital
or
Inserting the 1PosSSI/Digital in an energized state
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
5.7 CPU /Master Stop and RESET State
Response of the 1PosSSI/Digital
The current run is stopped.
All 3 digital outputs are set to 0.
Feedback bit POS_ERR = 0
Feedback bit POS_DONE = 1
Response of the 1PosSSI/Digital
The feedback interface of the 1PosSSI/Digital remains
current.
The axis remains synchronized, and the actual value is
current.
The moved encoder range remains valid.
The changed switch-off and switchover differences and the
path difference for the monitoring of the direction of rotation
remain valid.
An initiated JOB 10: Latch function remains active.
The feedback bit selected with JOB 15 is current.
Response of the 1PosSSI/Digital
The axis is synchronized, and the actual value corresponds
to the current encoder value.
The encoder range has not been moved.
The switch-off and switchover difference is accepted from
the parameters.
The path difference for the monitoring of the direction of
rotation is set at double the switch-off difference.
JOB 10: Latch function is not active.
The residual distance is displayed as a feedback value.