FIG. 11
Panel calibration
4.
Follow the instructions, touching the crosshairs in order across the screen.
5.
The page will read "Calibration Successful. Touch to continue." Touch anywhere on the screen to return to the
Calibration page.
If the screen is not touched at that point, the device will automatically return to the
Calibration page within 10 seconds.
In certain circumstances, you may wish to test the calibration of a panel without actually recalibrating it. The Calibration
Test page (FIG. 12) may be used to verify the accuracy of that calibration.
To calibrate the touch panel:
1.
From the Settings page, select Display.
2.
From the Display page, select Calibration.
3.
To test the calibration of the touch panel, select Calibration Test to open the Calibration Test page (FIG. 12).
FIG. 12
Calibration Test page
4.
Touch the screen and note the positioning of the crosshairs based on where you touch.
5.
If the crosshairs do not match the places where you touch, then go back to calibrate the panel.

Calibration Test

Unlike previous AMX touch panels, the Modero X and S Series panels are self-calibrated on startup. The Calibration
Test page (FIG. 13) may be used to verify the accuracy of that calibration.
FIG. 13
Calibration Test page
To run a calibration test on the panel:
1.
From the Settings page, select Display.
Modero G4 Touch Panels - Configuration and Programming
Settings Pages
9