Remote Keypad Communications Error; Cpu Error - IMO Jaguar CUB Instruction Manual

Compact inverter
Table of Contents

Advertisement

Possible Causes
(2) A high intensity noise was
given to the inverter while
data (especially initializing
data) was being written.
(3) The CPU did not operate
normally.
E 2
[ 13 ]

Remote keypad communications error

Problem
A communications error occurred between the remote keypad and the inverter.
Possible Causes
(1) Break in the
communications cable or
poor contact.
(2) A high intensity noise was
given to the inverter.
(3) The remote keypad
malfunctioned.
(4) The RS485
communications card
malfunctioned.
[ 14 ]
E 3

CPU error

Problem
A CPU error (e.g. erratic CPU operation) occurred.
Causes
(1) A high intensity noise was
given to the inverter.
(2) The printed control circuit
board in the inverter
malfunctioned.
What to Check and Suggested Measures
Check if appropriate noise control measures have been
implemented (e.g., correct grounding and routing of control
and main circuit wires). Alternatively, perform the same check
as described in (1) above.
Improve noise control. Alternatively, return the initialized
function code data to their previous settings, then restart the
operation.
Initialize the function code data by setting H03 to 1, then reset
the alarm by pressing the
key and check that the alarm
goes on.
This problem was caused by a printed circuit board (PCB)
(including the CPU) malfunction, so it is necessary to
replace the PCB. Contact IMO.
What to Check and Suggested Measures
Check continuity of the cable, contacts and connections.
Replace the cable.
Check if appropriate noise control measures have been
implemented (e.g., correct grounding and routing of control
and main circuit wires).
Improve noise control.
E 2
Check that alarm
does not occur if you connect another
remote keypad to the inverter.
Replace the remote keypad.
E 2
Check that alarm
does not occur even if you connect
another remote keypad to the inverter.
Replace the card.
What to Check and Suggested Measures
Check if appropriate noise control measures have been
implemented (e.g. correct grounding and routing of control
and main circuit wires).
Improve noise control.
Contact IMO.
6-16