IMO Jaguar CUB Instruction Manual page 37

Compact inverter
Table of Contents

Advertisement

Symbol
Name
[X1]
Digital
(1) The various signals such as coast-to-stop, alarm from external equip-
input 1
ment, and multistep frequency selection can be assigned to terminals
[X1] to [X3], [FWD] and [REV] by setting function codes E01 to E03, E98,
[X2]
Digital
and E99. For details, refer to Chapter 5, Section 5.2 "Overview of
input 2
Function Codes."
(2) Input mode, i.e. Sink/Source, is changeable by using the internal jumper
[X3]
Digital
switch.
input 3
(3) Switches the logic value (1/0) for ON/OFF of the terminals between [X1]
[FWD]
Forward
to [X3], [FWD] or [REV], and [CM]. If the logic value for ON between [X1]
operation
and [CM] is 1 in the normal logic system, for example, OFF is 1 in the
command
negative logic system and vice versa.
[REV]
Reverse
(4) The negative logic signaling cannot be applicable to [FWD] and [REV].
operation
command
Digital input circuit specifications
[PLC]
PLC
Connects to PLC output signal power supply. (Rated voltage: +24 VDC,
signal
Maximum output current: 50 mA)
power
[CM]
Digital
Common terminal for digital input signals
common
This terminal is electrically isolated from terminals [11] and [Y1E].
Table 2.8 Continued
Functions
Item
Operation
ON level
voltage
OFF level
(SINK)
Operation
ON level
voltage
(SOURCE) OFF level
Operation current at ON
(Input Voltage at 0 V)
Allowable leakage
current at OFF
2-16
Min.
Max.
0V
2V
22V
27V
22V
27V
0V
2V
2.5mA
5mA
-
0.5mA