For three-phase 200V and single-phase 200V series inverters
The braking level setting for the three-phase 200V and single-phase 200V
series should be calculated from the DC braking level I
reference current I
Setting
(%)
(Example) Setting the braking level I
dard motors
Applicable motor
rating (kW)
Reference
current Iref (A)
The brake function of the inverter does not provide mechanical holding means.
Otherwise injuries could occur.
F23, F25
Starting Frequency and Stop Frequency
At the startup of an inverter, the initial output frequency is equal to the starting fre-
quency. The inverter stops its output at the stop frequency.
Set the starting frequency to a level that will enable the motor to generate enough
torque for startup. Generally, set the motor's rated slip frequency to F23.
If the starting frequency is lower than the stop frequency, the inverter will
not output any power as long as the set frequency does not exceed the
stop frequency.
F26, F27
Motor Sound (Carrier frequency and Tone)
Motor Sound (Carrier frequency) (F26)
Changing the carrier frequency
may decrease the motor run-
ning noise, leakage current from
the output lines, and electric
noise from the inverter.
(A), as shown below.
ref
I
(A)
DB
=
100
I
(A)
ref
at 4.2 Amp (A) for 0.75 kW stan-
DB
4.2
(A)
Setting
(%)
=
100
84
5.0
(A)
N/A
N/A
0.4
N/A
N/A
3.0
Carrier frequency
Motor running noise
Output current waveform
Leakage current level
Electric noise level
5-24
(A) based on the
DB
0.75
1.5
2.2
4.0
5.0
8.0
11.0
17.0
0.75
15 kHz
Noisy
quiet
Poor
good
Low
high
Low
high