Chapter 9 List Of Peripheral Equipment And Options - IMO Jaguar CUB Instruction Manual

Compact inverter
Table of Contents

Advertisement

Chapter 9
LIST OF PERIPHERAL EQUIPMENT AND OPTIONS
The table below lists the main peripheral equipment and options that are connected to the Jaguar
CUB. Use them in accordance with your system requirements.
Name of
peripheral
equipment
Moulded case
MCCBs are designed to protect the power circuits between the power control
circuit breaker
board and inverter's main terminals (L1/R, L2/S and L3/T for three-phase
(MCCB)
power, L1/L and L2/N for single-phase power) from overload or short-circuit
which in turn prevents secondary disasters caused by the inverter
Residual-current-
malfunctioning.
operated
RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and
protective device
RCDs/ELCBs that satisfy the recommended rated current listed below.
(RCD)
/Earth leakage
circuit breaker
(ELCB) *
* With the
exception of
those
exclusively
designed for
protection from
ground faults
Note 1) A box ( ) in the above table replaces E suffix for filtered version
The rated current and circuit breaking capacity depend on the power supply
voltage.
Function and application
Applicable
Power
motor
supply
Inverter type
rating
voltage
(kW)
0.4
CUB3A-2
0.75
CUB5A-2
Three-
phase
1.5
CUB8A-2
200 V
2.2
CUB11A-2
4.0
CUB17A-2
0.4
CUB1A5-4
0.75
CUB2A5-4
Three-
phase
1.5
CUB3A7-4
400 V
2.2
CUB5A5-4
4.0
CUB9A-4
0.4
CUB3A-1
Single-
0.75
CUB5A-1
phase
1.5
CUB8A-1
200 V
2.2
CUB11A-1
9-1
Recommended rated
current (A) of
MCCB and RCD/ELCB
w/ DC
w/o DC
reactor
reactor
5
5
10
15
10
20
20
30
5
5
10
15
10
20
5
5
10
10
15
20
20
30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents