8.6 Protective Functions

Name
Overcurrent
- Stops the inverter output to protect the inverter
protection
from an overcurrent resulting from overload.
- Stops the inverter output to protect the inverter
from an overcurrent due to a short circuit in the
output circuit.
- Stops the inverter output to protect the inverter
from an overcurrent due to a ground fault in the
output circuit. This protection is effective only
when the inverter starts. If you turn on the
inverter without removing the ground fault, this
protection may not work.
Overvoltage
The inverter stops the inverter output by detecting
protection
an overvoltage (400 VDC for 200V series, 800
VDC for 400V series) in the DC link circuit.
This protection is not assured if excess AC line
voltage is applied inadvertently.
Undervoltage
Stops the inverter output when the DC link circuit voltage drops
protection
below the undervoltage level (200 VDC for 200 V series, 400 VDC
for 400 V series).
However, if data "4 or 5" is selected for F14, no alarm is output
even if the DC link circuit voltage drops.
Input phase
Detects input phase loss, stopping the inverter output. This
loss protection
function prevents the inverter from undergoing heavy stress that
may be caused by input phase loss or interphase voltage
unbalance exceeding 6% and may damage the inverter.
If connected load is light or a DC reactor is connected to the
inverter, this function will not detect input phase loss if any.
In single-phase series of inverters, this function is disabled by
factory default.
Output phase
Detects breaks in inverter output wiring at the start of running and
loss protection
during running, stopping the inverter output.
Inverter
- Stops the inverter output by detecting excess heat sink
temperature in case of cooling fan failure or overload.
Braking
- When the built-in or external braking resistor overheats, the
resistor
inverter stops running.
* It is necessary to set the function code data corresponding to
the resistor used (built-in or external).
Overload
Stops the inverter output if the Insulated Gate Bipolar Transistor
protection
(IGBT) internal temperature calculated from the output current and
cooling fan temperature detection is over the preset value.
Electronic
In the following cases, the inverter stops running the motor to
thermal
protect the motor in accordance with the electronic thermal
overload
function setting.
relay
- Protects general-purpose motors over the entire frequency
range.
- Protects inverter motors over the entire frequency range.
* The operation level and thermal time constant can be set.
*1
This alarm may not be outputted depending upon the data setting of the function code.
Description
During
acceleration
During
deceleration
During running
at constant
speed
During
acceleration
During
deceleration
During running
at constant
speed
(Stopped)
8-13
LED
Alarm
monitor
output
displays
[30A,B,C]
O C 1
Yes
O C 2
O C 3
O U 1
Yes
O U 2
O U 3
*1
L U
Yes
L
Yes
O P L
Yes
O H 1
Yes
d b H
Yes
O L U
Yes
O L 1
Yes