Outputting the output current in an analogue format (FMA) (F31 = 2)
The analogue output terminal [FMA] outputs 10 V, that is, 200% of the
reference current I
(A), supposing the output gain selected with F30 as
ref
100%. For three-phase 200V and single-phase 200V series, therefore,
you need to set the output gain (F30) based on the conversion result ob-
tained by the following expression:
Conversion expression for calculating the output gain which is required
for outputting the voltage V (V) via terminal [FMA] when current I (A)
flows across the inverter
I
(A)
V
(V)
ref
Output
gain
=
2
I
(A)
10
(V)
The reference current is given in the table for F20 to F22 on page
5-24.
According to the conversion result, the output voltage to terminal [FMA]
can be calculated as shown below.
Analogue
output
voltage
(V)
=
2
(Example) Outputting analogue voltage 8V for 0.75 kW standard motors
when the inverter output current is 4.2A
5.0
(A)
8
(V)
Output
gain
=
2
4.2
(A)
10
Analog
output
voltage
(V)
=
2
5-26
100
I
(A): Reference current (A)
ref
I
(A)
Output
gain
(F30)
10
(V)
I
(A)
100
ref
100
190.4
(V)
4.2
(A)
190
10
(V)
7.98
5.0
(A)
100