Table 3.13 Maintenance Display Items
LED Monitor
Display contents
shows:
5_00
Accumulated
Shows the accumulated power-ON time of the inverter.
run time
Unit: thousands of hours.
When the total ON-time is less than 10,000 hours (display: 0.001 to
9.999), it is possible to check data in hourly units. When the total time
is 10,000 hours or more (display: 10.00 to 65.53), the display will
change to units of 10 hours. When the total time exceeds 65,535
hours, the display will be reset to 0 and the count will start again.
5_01
DC link circuit
Shows the DC link circuit voltage of the inverter.
voltage
Unit: V (volts)
5_03
Max. temperature
Shows the maximum temperature of the heat sink for every hour.
of heat sink
Unit: ºC
5_04
Max. effective
Shows the maximum effective current for every hour.
current
Unit: A (amperes)
5_05
Capacitance of
Shows the current capacitance of the DC bus capacitor, based on the
the DC bus
capacitance when shipping as 100%. Refer to Chapter 7 "MAINTE-
capacitor
NANCE AND INSPECTION" for details.
Unit: %
5_06
Accumulated
Shows the accumulated run time of the capacitor mounted on the
run time of
printed circuit board.
electrolytic
The display method is the same as for "accumulated run time" above.
capacitor on the
However, when the total time exceeds 65,535 hours, the count stops
printed circuit
and the display remains at 65.53.
board
5_07
Accumulated
Shows the accumulated run time of the cooling fan.
run time of the
The cooling fan ON/OFF control (function code H06) is effective, so
cooling fan
the time when the fan is stopped is not counted.
The display method is the same as for "accumulated run time" above.
However, when the total time exceeds 65,535 hours, the count stops
and the display remains at 65.53.
5_08
Number of
The motor run times (the number of times the inverter run command is
startups
set to on) are calculated and displayed.
1.000 indicates 1,000 times. When any number ranging from 0.001 to
9.999 is displayed, the display increases by 0.001 per startup, and
when any number from 10.00 to 65.53 is displayed, the display in-
creases by 0.01 every 10 startups. When the total number exceeds
65,535, the display will be reset to 0 and the count will start again.
5_11
No. of RS485
Shows the total number of times RS485 communications error has
errors
occurred after the power is turned on.
Once the number of errors exceeds 9.999, the display (count) returns
to 0.
5_12
RS485 error
Shows the latest error that has occurred with RS485 communications
contents
in hexadecimal format.
5_14
ROM version of
Shows the ROM version of the inverter as a 4-digit display.
inverter
5_16
ROM version of
Shows the ROM version of the keypad panel as a 4-digit display. (For
keypad panel
remote keypad only.)
Description
3-24