Table 3-1: Wire Sizes - Ametek CSW5550 User Manual

Csw series ac power source
Table of Contents

Advertisement

User Manual
C
1:
OLUMN
SIZE
(AWG)
14
12
10
8
6
4
2
1/0
3/0
The output power cables must be large enough to prevent a total voltage drop exceeding 1% of
the rated output voltage between the power source and the load. Table 3-1 shows the AWG size
of the cables that may be used. Cable lengths must not exceed twenty-five (25) feet. For lengths
greater than 25 feet, calculate the voltage drop from the following formula:
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
CSW Series
C
2:
OLUMN
AMPERES
OHMS/100 FEET
(MAXIMUM)
(ONE WAY)
15
20
30
40
55
70
95
125
165
Recommended Wire Gauge Selection Guide
LOAD CURRENT
22 AMPS
37 AMPS
74 AMPS
111 AMPS

Table 3-1: Wire Sizes

C
3:
OLUMN
IR DROP/100 FEET
(COL. 2 X COL. 3)
0.257
0.162
0.102
0.064
0.043
0.025
0.015
0.010
0.006
WIRE GAGE
10 AWG
8 AWG
4 AWG
2 AWG
California Instruments
C
4:
OLUMN
3.85
3.24
3.06
2.56
2.36
1.75
1.42
1.25
1.04
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents