Ametek Sorensen XHR Series Operation Manual

Ametek Sorensen XHR Series Operation Manual

1000 watt programmable dc power supply
Table of Contents

Advertisement

XHR 1000 Watt Series
Programmable DC
Power Supply
Operation Manual
XHR 7.5-130
XHR 20-50
XHR 33-33
XHR 40-25
XHR 60-18
XHR 100-10
XHR 150-7
XHR 300-3.5
XHR 600-1.7
TM-XROP-01XN Rev C
www.programmablepower.com

Advertisement

Table of Contents
loading

Summary of Contents for Ametek Sorensen XHR Series

  • Page 1 XHR 1000 Watt Series Programmable DC Power Supply Operation Manual XHR 7.5-130 XHR 20-50 XHR 33-33 XHR 40-25 XHR 60-18 XHR 100-10 XHR 150-7 XHR 300-3.5 XHR 600-1.7 TM-XROP-01XN Rev C www.programmablepower.com...
  • Page 3 About AMETEK AMETEK Programmable Power, Inc., a Division of AMETEK, Inc., is a global leader in the design and manufacture of precision, programmable power supplies for R&D, test and measurement, process control, power bus simulation and power conditioning applications across diverse industrial segments.
  • Page 4 This page intentionally left blank.
  • Page 5 Neither AMETEK Programmable Power Inc., San Diego, California, USA, nor any of the subsidiary sales organizations can accept any responsibility for personnel, material or inconsequential injury, loss or damage that results from improper use of the equipment and accessories.
  • Page 6 This page intentionally left blank.
  • Page 7 AMETEK will, at its expense, deliver the repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the Buyer is in default under the Purchase Order Agreement or where the Product or any part...
  • Page 8 This page intentionally left blank.
  • Page 9: Table Of Contents

    Contents About This Manual ........... vii List of Figures .
  • Page 10 Local and Remote Sensing ..........48 Sense Wiring .
  • Page 11: List Of Figures

    List of Figures Figure 1.1 Power Supply Front Panel ....... . 17 Figure 1.2 Rear Panel with Bus Bar.
  • Page 12 List of Figures Operating Manual for XHR Series Power Supply...
  • Page 13: List Of Tables

    List of Tables Table 1.1 SW1 Switch Functions ........20 Table 1.2 Electrical Specifications for 7.5 V to 40 V Models .
  • Page 14 List of Tables Operating Manual for XHR Series Power Supply...
  • Page 15: Description

    Section 1. Features and Specifications Description The 1000 watt DC output power supplies provide low noise, precisely regulated, variable DC output. Typically they are used for bench and automated test equipment (ATE) applications. Each unit includes over voltage protection and thermal shutdown as standard features.
  • Page 16: Front Panel Controls

    Features and Specifications Front Panel Controls • Remote analog voltage and current limit programming with selectable programming ranges. • External monitor signals for output voltage and current. • Isolated analog remote programming control of the output voltage or current and isolated readback of output voltage and current with the optional ISOL interface.
  • Page 17: Figure 1.1 Power Supply Front Panel

    Features and Specifications Front Panel Controls Shutdown LED (S/D) (See page 61 for more information.) OVP Shutdown Standby Switch (STANDBY) LED (OVP) (See page 61.) Local Voltage and Current Remote Programming LED (REM) Limit Setting Preview Switch (See page 67.) (V/I CHECK) (See page 37.) Return to Local Programming (LOCAL)
  • Page 18: Rear Panel Connectors And Switch

    Features and Specifications Rear Panel Connectors and Switch Rear Panel Connectors and Switch The output terminals for the low voltage models (7.5 V to 40 V) are bus bars. The high voltage models (60 V to 600 V) use a wire clamp connector. See Figure 1.2 and Figure 1.3 to identify the switches and connectors on the rear panel.
  • Page 19: Sw1 Programming Switch

    Features and Specifications Rear Panel Connectors and Switch 100/120/200/240V 50/60 HZ 1300VA Local Sense Wires DC Output and Local Sense Connector (See page 48.) (See page 39 for more information.) Figure 1.3 Rear Panel with High Voltage Output Connector (For 60 V to 600 V models.) The SW1 Programming, Monitoring, and Shutdown Select switch is an 8-position Programming piano DIP switch located on the power supply’s rear panel.
  • Page 20: J2 Programming Connector

    Features and Specifications Rear Panel Connectors and Switch See Table 1.1 for a list of the functions assigned to each SW1 switch. Table 1.1 SW1 Switch Functions Switch Function OFF (Open) ON (Closed) SW1-1 1 mA current source for resistive Voltage source Resistive programming of output voltage.
  • Page 21: Figure 1.5 J2 Programming Connector

    Features and Specifications Rear Panel Connectors and Switch See Figure 1.5 to identify the function of each of the 12 terminals on the J2 connector. Wire Clamp Return Sense (–SNS) Connector Screw Positive Sense (+SNS) Control Ground ( Remote Output Voltage Programming Select (VRMT) Remote Current Limit Programming Select (IRMT) Program/Monitor Signal Return (PGM–) Output Voltage Programming Input (VPGM)
  • Page 22 Features and Specifications Rear Panel Connectors and Switch Wiring WARNING There is a potential shock hazard at the output and J2 terminals when using a power supply with a rated output greater than 40 V. Use load wiring with a minimum insulation rating equivalent to the maximum output voltage of the power supply.
  • Page 23: Specifications

    Features and Specifications Specifications Specifications Electrical Specifications are warranted over a temperature range of 0 to 40 °C with default local sensing. Specifications The tables on the following pages post maximum values for model-dependent specifications. Specifications which are different due to measurements being taken at the front panel binding posts are identified, where they occur, in the tables.
  • Page 24 Features and Specifications Specifications Table 1.2 Electrical Specifications for 7.5 V to 40 V Models Models 7.5-130 20-50 33-33 40-25 Output Ratings: Output Voltage 0-7.5 V 0-20 V 0-33 V 0-40 V Output Current 0-130 A 0-50 A 0-33 A 0-25 A Output Power 975 W...
  • Page 25 Features and Specifications Specifications Table 1.3 Electrical Specifications for 60 V to 600 V Models Models 60-18 100-10 150-7 300-3.5 600-1.7 Output Ratings: Output Voltage 0-60 V 0-100 V 0-150 V 0-300 V 0-600 V Output Current 0-18 A 0-10 A 0-7 A 0-3.5 A 0-1.7 A...
  • Page 26: Additional Electrical Specifications

    Features and Specifications Additional Electrical Specifications Additional Electrical Specifications Voltage Mode Transient Response 1 ms (Time for the output voltage to recover within 0.5% of its previous level after a step change in load current of up to 50% of the rated output.) Time delay from power on until 4 s maximum...
  • Page 27: Electrical Characteristics

    Features and Specifications Electrical Characteristics Electrical Characteristics Switching Frequency 7.5 V to 300 V models: nominal 125 kHz (250 kHz output ripple) 600 V model nominal 62.5 kHz (125 kHz output ripple) Output Hold-up Time Greater than 10 ms with interruption of AC line, for nominal AC input and full load.
  • Page 28: Environmental Specifications

    Features and Specifications Environmental Specifications Environmental Specifications Operating Ambient Temperature 0 to 40 °C. Storage Temperature Range – 40 ° to 85 °C Humidity Range Up to 80% RH, non-condensing Operating Altitude Up to 6,500 feet (2000 m) Installation Category Pollution Degree Approvals Units marked with c(CSA)us are CSA certified to:...
  • Page 29: Mechanical Specifications

    Features and Specifications Mechanical Specifications Mechanical Specifications Front Panel Voltage and Current 10-turn voltage and current potentiometers Control Front Panel Voltage Control 0.02% of maximum voltage Resolution Front Panel Voltage and Current 3.5-digit numeric LED displays (for accuracy Meters specifications, see Table 1.2 and Table 1.3) AC Input Connector Type IEC 320 Connector, appropriate power cord for destination country.
  • Page 30: Dimensions

    Features and Specifications Dimensions Dimensions 18.78 in. (477 mm) 15.85 in. (403 mm) 16.18 in. (411 mm) 8.45 in. (215 mm) 3.43 in. 3.14 in. (87 mm) (79 mm) Figure 1.6 Dimensional Drawings (Dimensions given are nominal.) Operating Manual for XHR Series Power Supply...
  • Page 31: Basic Setup Procedure

    Section 2. Installation Basic Setup Procedure Table 2.1 for a summary of the basic setup procedure and an overall view of the information in this section. Use the procedure as a quick reference if you are familiar with the installation requirements for the power supply. If you want more information, each step in the procedure refers to sections which contain more details.
  • Page 32: Inspection, Cleaning, And Packing

    Installation Inspection, Cleaning, and Packing Inspection, Cleaning, and Packing Initial When you first receive your unit, perform a quick physical check. Inspection 1. Ensure that each package contains the power supply and an AC input cord. 2. Inspect the unit for scratches and cracks, and for broken switches, connectors, and displays.
  • Page 33: Returning Power Supplies To The Manufacturer

    Installation Returning Power Supplies to the Manufacturer Returning Power Supplies to the Manufacturer Return Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA) number and the correct factory “Ship To” address. Products Material must also be shipped prepaid. Product shipments will be refused and returned at your Authorization expense if they are unauthorized, returned without an RMA number clearly marked Policy...
  • Page 34: Packaging For Shipping Or Storage

    Installation Returning Power Supplies to the Manufacturer Packaging for Follow these instructions to prepare the unit for shipping or storage. Shipping or 1. When returning the unit or sending it to the service center, attach a tag to the unit Storage stating its model number (available from the front panel label) and its serial number (available from the rear panel label).
  • Page 35: Location, Mounting, And Ventilation

    Installation Location, Mounting, and Ventilation Location, Mounting, and Ventilation Rack Mounting CAUTION Ensure that any rack mounting screws do not extend more than 1/4in. (6.3 mm) into the base of the unit. The rack mount kit allows you to mount two units side by side in a standard 19in. (483 mm) rack space.
  • Page 36: Ac Input Power

    Installation AC Input Power AC Input Power WARNING There is a potential shock hazard if the power supply chassis and cover are not connected to an electrical ground via the safety ground in the AC input connector. Ensure that the power supply is connected to a grounded AC outlet with the recommended AC input connector configured for the available line voltage CAUTION...
  • Page 37: Functional Tests

    Installation Functional Tests Functional Tests The functional test procedures include power-on and front panel function checks as well as voltage and current mode operation checks. • Equipment Digital voltmeter (DVM) rated better than 0.5% accuracy. Required • DC shunt 1 mV/A (±0.25%) with connecting wire. The recommended current ratings for the DC shunt and the wire must be at least 10% more than the output current of the power supply.
  • Page 38: Current Mode Operation Check

    Installation Functional Tests Current Mode 1. Ensure that the front panel power switch is set to OFF. Operation 2. Turn the voltage and current controls on the front panel fully counter-clockwise. Check 3. Turn the voltage control one (1) or two (2) turns clockwise. 4.
  • Page 39: Load Connection

    Installation Load Connection Load Connection This section provides recommendations for load wires and how to connect them for both single and multiple load configurations. Load Wiring When connecting load wiring to the power supply, consider the following factors: • Current capacity and voltage rating of the wire •...
  • Page 40: Figure 2.2 Maximum Load Wire Length For 1 V Line Drop

    Installation Load Connection Load Wiring Length for Operation with Sense Lines For applications using remote sensing, you must limit the voltage drop across each load line. Figure 2.2 shows some maximum allowable wire lengths for a given load current and wire size. We recommend that you use the larger load wiring to ensure a smaller voltage drop (1 V typical maximum), although the units (except 7.5 V models) will compensate for up to 5 V drop in each line.
  • Page 41: Making Load Connections

    Installation Load Connection Making Load Connections WARNING There is a potential shock hazard at the load when using a power supply with a rated output greater than 40 V. To protect personnel against accidental contact with hazardous voltages, ensure that the load, including connections, has no live parts which are accessible.
  • Page 42: Inductive Loads

    Installation Load Connection Shield Flat Washer (3 places) 1/4in. Screw (2 places) A16 EMI Filter Bus Bar Capacitor 3/8in. Screw (1 place) Figure 2.3 Bus Bar Shield Inductive Use the following protection methods only when using local sensing. Loads To prevent damage to the power supply from inductive kickback, connect a diode across the output.
  • Page 43: Figure 2.4 Typical Load Connection Hardware

    Installation Load Connection Wire Terminal Lug (2 places) Screw (2 places) Lock Washer (2 places) Hex Nut (2 places) Figure 2.4 Typical Load Connection Hardware (For 7.5 V to 40 V models.) To make load connections to a 7.5 V, 130 A power supply: 1.
  • Page 44: Figure 2.5 Output Connector

    Installation Load Connection 60 V to 600 V Models WARNING To protect personnel against accidental contact with hazardous voltages, ensure that the load, including connections, has no live parts which are accessible. Also ensure that the insulation rating of the load wiring and circuitry is greater than or equal to the maximum output voltage of the power supply.
  • Page 45: Connecting Single Loads

    Installation Load Connection Connecting Figure 2.6 Figure 2.7 show recommended load and sensing connections for single loads. Local sense lines shown are default J2 connections. Single Loads You do not need remote sensing for basic operation of your supply. However, if you wish to correct for any small drops in your load lines, then use this feature.
  • Page 46: Figure 2.8 Multiple Loads With Local Sensing

    Installation Load Connection Radial Power Distribution Method To connect distributed loads, we recommend that you use radial power distribution. With this method, you connect power to each load individually from a single pair of terminals designated as the positive and negative distribution terminals. These terminals may be the power supply output terminals, the terminals of one of the loads, or a distinct set of terminals especially established for distribution use.
  • Page 47: Figure 2.9 Multiple Loads With Remote Sensing

    Installation Load Connection Figure 2.9 Multiple Loads with Remote Sensing...
  • Page 48: Local And Remote Sensing

    Installation Local and Remote Sensing Local and Remote Sensing Use connections on the rear panel J2 connector to set up the power supply for local or remote sensing of output voltage. Sense Wiring WARNING There is a potential shock hazard at the sense connector when using a power supply with a rated output greater than 40 V.
  • Page 49 Installation Local and Remote Sensing Use remote sensing during voltage mode operation to shift the power supply’s regulation point from its output terminals to the load or distribution terminals by using a separate pair of wires to allow the control circuitry to monitor the load voltage.
  • Page 50: Figure 2.10Connecting Remote Sense Lines

    Installation Local and Remote Sensing Figure 2.10Connecting Remote Sense Lines Operating Manual for XHR Series Power Supply...
  • Page 51: Standard Operation

    Section 3. Local Operation Standard Operation Once you have installed the power supply as covered in Section 2. Installation, the power supply is ready to operate in local control mode (that is, operation at the front panel). The power supply has two basic operating modes: Constant Voltage Mode and Constant Current Mode, and two control modes: Local Control Mode (default setting) and Remote Programming Mode.
  • Page 52: Figure 3.1 Operating Modes

    Local Operation Standard Operation Output Voltage > Constant Voltage Mode Region Crossover Point V SET < Constant Current Mode Region Where: = Load Resistance = Output Voltage Setting Output Current = Output Current Setting I SET Figure 3.1 Operating Modes Constant Voltage Mode Operation The power supply will operate in constant voltage mode whenever the load current I is less than the current limit setting I...
  • Page 53: Shipped Configuration (Local Control Mode)

    Local Operation Standard Operation The factory ships units already configured for local control (front panel) operation. Shipped Table 3.1 summarizes this configuration. Configuration (Local Control Table 3.1 Shipped Configuration (Local Control Mode) Mode) Local Control Configuration Additional References Use the front panel controls to adjust the Section 3 covers front panel output voltage and current limit settings.
  • Page 54: Using Multiple Supplies

    Local Operation Using Multiple Supplies Using Multiple Supplies WARNING There is a shock hazard at the load when using a power supply with a rated or combined output greater than 40 V. To protect personnel against accidental contact with hazardous voltages created by series connection, ensure that the load, including connections, has no live parts which are accessible.
  • Page 55: Configuring Multiple Supplies For Series Operation

    Local Operation Using Multiple Supplies Configuring Multiple Supplies for Series Operation CAUTION Do not use remote sensing during series operation. CAUTION The maximum allowable sum of the output voltages is 600 Vdc. Use series operation to obtain a single higher voltage output using two or more supplies.
  • Page 56: Configuring Multiple Supplies For Parallel Operation

    Local Operation Using Multiple Supplies Configuring Use parallel operation to obtain a higher current through a single output using two or more supplies. Set all of the OVP set points to maximum. Set all of the outputs to the Multiple same voltage before connecting the positive (+) output terminals and negative (–) Supplies for output terminals in parallel.
  • Page 57: Configuring Multiple Supplies For Split Supply Operation

    Local Operation Using Multiple Supplies Configuring Split supply operation uses two power supplies to obtain two positive voltages with a common ground, or to obtain a positive-negative supply. Multiple Supplies for Two Positive Voltages To obtain two positive voltages, connect the negative Split Supply output terminals of both supplies together in a common connection.
  • Page 58: Figure 3.5 Split Supply Operation Of Multiple Supplies

    Local Operation Using Multiple Supplies Positive-negative Supply CAUTION To prevent possible damage to the supply, do not connect the remote program return line of the negative supply to the common connection. To obtain a positive-negative supply, connect the negative output terminal of one supply to the positive output terminal of the second supply.
  • Page 59: Using Over Voltage Protection (Ovp)

    Local Operation Using Over Voltage Protection (OVP) Using Over Voltage Protection (OVP) The OVP circuit protects the load in the event of a remote programming error, an incorrect voltage control adjustment, or a power supply failure. The protection circuit monitors the output voltage and will shut down the main power converter whenever a preset voltage limit is exceeded.
  • Page 60: Resetting The Ovp Circuit

    Local Operation Using Over Voltage Protection (OVP) Resetting the To reset the OVP circuit after it activates: OVP Circuit 1. Reduce the power supply’s output voltage setting to below the OVP set point. 2. Press the STANDBY switch IN. The S/D (Shutdown) LED on the front panel will turn on.
  • Page 61: Using The Shutdown Function

    Local Operation Using the Shutdown Function Using the Shutdown Function Use the Shutdown function to disable or enable the supply’s output so that you can make adjustments to either the load or the power supply without shutting off the entire supply. Activate this function from the front panel at any time by using the STANDBY switch.
  • Page 62: Figure 3.6 Shutdown Programming With Active Low Signal

    Local Operation Using the Shutdown Function Shutdown Signal SW1-7: Source: OFF (OPEN) High = Output OFF Low = Output ON Figure 3.6 Shutdown Programming with Active Low Signal SW1-7: Shutdown Signal ON (CLOSED) Source: High = Output ON Low = Output OFF Figure 3.7 Shutdown Programming with Active High Signal Operating Manual for XHR Series Power Supply...
  • Page 63: Over Temperature Protection (Otp)

    Local Operation Over Temperature Protection (OTP) Over Temperature Protection (OTP) The over temperature protection circuit shuts down the power supply’s output when the power supply exceeds internal temperature limits. When an OTP shutdown occurs, the OTP LED on the front panel turns on. You can select the way that the power supply recovers from an over temperature shutdown by setting the SW1-8 switch on the rear panel.
  • Page 64: User Diagnostics

    Local Operation User Diagnostics User Diagnostics If your power supply is not performing as described in this manual, run through the procedures and checks in this section before calling your service technician. These procedures are confined to operator-level functions only and do not require cover-off servicing.
  • Page 65 Local Operation User Diagnostics Table 3.4 Quick Diagnostics Symptom Check Further Checks and Corrections No output and the Is input voltage in the specified range? Connect to appropriate voltage source. display is blank. Power switch ON? Turn on power. Internal circuit. See your service technician.
  • Page 66 Local Operation User Diagnostics Symptom Check Further Checks and Corrections Output voltage Is unit at current limit? Increase current limit setting or reduce “Standard Operation” on page fluctuating or load. See regulation poor. Is input voltage within specified range? Connect to appropriate AC voltage source.
  • Page 67: Remote Analog Programming Of Output Voltage And Current Limit

    Section 4. Remote Operation Remote Analog Programming of Output Voltage and Current Limit CAUTION Ensure that you make connections to the J2 connector exactly as shown in each procedure in this section. Incorrect J2 jumper connections may damage the supply. Remote analog programming allows control of the output voltage and/or current limit to shift from local operation at the front panel controls to external analog sources.
  • Page 68: Remote Analog Programming Procedure

    Remote Operation Remote Analog Programming of Output Voltage and Current Limit Remote Analog Programming Procedure CAUTION To maintain the isolation of the power supply output and prevent ground loops, use an isolated (ungrounded) programming source when operating the power supply via remote analog control at the J2 connector. CAUTION The remote programming inputs are internally referenced to the supply's negative output.
  • Page 69 Remote Operation Remote Analog Programming of Output Voltage and Current Limit Table 4.1 Power Supply Settings for Different Programming Sources Output Current Limit Programming Source Output Voltage Programming None (Front 0-5 Vdc 0-10 Vdc 0-5 k Resistor 0-10 k Resistor Source Panel Control) SW1: use...
  • Page 70: Sample Configuration

    Remote Operation Remote Analog Programming of Output Voltage and Current Limit Figure 4.1 Connecting Programming Sources to J2 Connector Sample The sample configuration in Figure 4.2 shows the required settings and connections Configuration for: • 0-10 Vdc programming of the output voltage •...
  • Page 71: Remote Monitoring Of Output Voltage And Current

    Remote Operation Remote Monitoring of Output Voltage and Current Remote Monitoring of Output Voltage and Current Readback The J2 connector on the rear panel provides access to calibrated readback signals for Signals remote monitoring of the output voltage and current. Use rear panel switches SW1-5 and SW1-6 to select either a 0-5 Vdc or a 0-10 Vdc range for the output.
  • Page 72: Using The Isolated Programming (Isol) Interface Option

    Remote Operation Using the Isolated Programming (ISOL) Interface Option SW1-5 and SW1-6 OFF (OPEN) Figure 4.4 0-10 Vdc Output Voltage and Current Monitoring Using the Isolated Programming (ISOL) Interface Option With the 4-channel Isolated (ISOL) Programming Interface installed, you can control and monitor the power supply’s output voltage and current limit using 0-5 V analog signals that are not referenced to the power supply’s internal ground.
  • Page 73: Isol Setup And Operating Instructions

    Remote Operation Using the Isolated Programming (ISOL) Interface Option ISOL Setup Operating Instructions CAUTION In order to maintain isolation, do not connect either J2 connector terminal 3 (control ground) or the power supply return to J2 terminal 6 (program/monitor signal return). 1.
  • Page 74 Remote Operation Using the Isolated Programming (ISOL) Interface Option Operating Manual for XHR Series Power Supply...
  • Page 75: Calibration Setup

    Section 5. Calibration Calibration Setup WARNING- HIGH ENERGY AND HIGH VOLTAGE Exercise caution when using and servicing a power supply. High energy levels can be stored at the output voltage terminals on a power supply in normal operation. In addition, potentially lethal voltages exist in the primary circuit and on the output and sense connectors of a power supply with a rated output greater than 40 V.
  • Page 76: Front Panel Calibration

    Calibration Front Panel Calibration Front Panel Calibration Front panel calibration includes voltmeter, ammeter, voltage and current preview and over voltage protection (OVP) setpoint and preview functions. Perform all procedures in the sequence give. Additional Make calibration adjustments using multiturn potentiometers accessed by removing the power supply’s cover.
  • Page 77: Ammeter Calibration

    Calibration Front Panel Calibration 3. Press the front panel STANDBY switch to its IN position. Check that the output voltage drops to 0V in less than 2 seconds. Check that the S/D LED turns on. 4. While holding the front panel V/I CHECK switch in, adjust the voltage check calibration potentiometer (R53) until the front panel meter reads the maximum rated output.
  • Page 78: Calibrating For Programming Accuracy

    Calibration Calibrating for Programming Accuracy Calibrating for Programming Accuracy WARNING Use a non-conducting, straight-bladed screwdriver to adjust the trim pots. The factory calibrates the offset and range of the voltage and current programming circuits to within 1% for the default 0-5 Vdc programming signals. You may need to recalibrate when you change SW1 switch settings to use 0-10 Vdc programming or when you switch back to 0-5 Vdc programming after previously calibrating for 0-10 Vdc programming.
  • Page 79: Voltage Programming Circuit Calibration

    Calibration Calibrating for Programming Accuracy Voltage 1. Ensure that the power supply is turned OFF. Disconnect any load. Programming 2. Connect the programming source between J2 terminals 7 (output voltage Circuit programming input) and 6 (program/monitor signal return). Calibration 3. Connect the DVM to the power supply output. 4.
  • Page 80: Calibrating For Readback Accuracy

    Calibration Calibrating for Readback Accuracy Calibrating for Readback Accuracy WARNING Use a non-conducting, straight-bladed screwdriver to adjust the trim pots. The factory calibrates the offset and range of the output voltage and current monitor circuits to within 1% for the default 0-5 Vdc scales. Recalibration may be necessary when you change SW1 switch settings to select the 0-10 Vdc scale or when you switch back to the 0-5 Vdc scale after previously calibrating for 0-10 Vdc operation.
  • Page 81: Output Voltage Monitor Circuit Calibration

    Calibration Calibrating for Readback Accuracy Output 1. Ensure that the power supply is turned OFF. Disconnect any load. Voltage 2. Connect a DVM across the power supply output to read the output voltage. Monitor 3. Connect a second DVM to the rear panel J2 terminals 9 (output voltage monitor) Circuit and 6 (program/monitor signal return).
  • Page 82: Output Current Monitor Circuit Calibration

    Calibration Calibrating for Readback Accuracy Output 1. Ensure that the power supply is turned OFF. Disconnect any load. Current 2. Connect the shunt and DVM across the power supply output to read the output Monitor current. Circuit 3. Connect a second DVM to the rear panel J2 terminals 10 (output current Calibration monitor) and 6 (program/monitor signal return).

Table of Contents