AutomationDirect CLICK PLC,
DirectLOGIC DL05, DL06, D0-DCM Module & DL105 PLCs
Panel Powered via external power supply, Port1 or Port2 Communications
PLC
Family
CPU
CLICK
all versions
all versions
Direct LOGIC
DL05
D0-DCM
all versions
Direct
LOGICDL06
D0-DCM
Direct LOGIC
all versions
DL105
* Note: The PLC can provide 5 VDC through this cable. No external 12-24 VDC souce is required, however, screen
brightness is diminished and the alarm beep will not function.
** Note: Wiring Diagrams for user constructed cables start on page 6-26.
®
PLC Compatibility & Connection Chart
PLC Port &
External DC Power Supply
Type
Using panel's RJ12 Port1
Protocol(s)
Supported
Port 1
AutomationDirect
RJ12 - 6 pin
Modbus (CLICK)
Port 1
K-sequence,
RJ12 - 6 pin
Direct NET,
Port 2
Modbus RTU
RJ12 - 6 pin
Port 1
RJ12 - 6 pin
K-sequence,
Direct NET,
Port 2
Modbus RTU
DB15HD
(female)
Port 1
RJ12 - 6 pin
K-sequence,
Direct NET,
Port 2
Modbus RTU
DB15HD
(female)
Port 1
RJ12 - 6 pin
K-sequence,
Direct NET,
Port 2
Modbus RTU
DB15HD
(female)
Port 1
K-sequence
RJ12 - 6 pin
EA1-MG6-USER-M Hardware User Manual, 1st Ed. Rev C, 09/10
Chapter 6: PLC Communications
C-more Micro-Graphic Panel
Panel to PLC Cabling Components Required for
Specific Port and Protocol being used.
*PLC Port Powered
or
Components &
Network Type
DV-1000CBL*
RS-232
DV-1000CBL*
RS-232
DV-1000CBL*
RS-232
DV-1000CBL*
+ FA-15HD
RS-232
DV-1000CBL*
RS-232
DV-1000CBL*
+ FA-15HD
RS-232
DV-1000CBL*
RS-232
DV-1000CBL*
+ FA-15HD
RS-232
DV-1000CBL*
RS-232
External DC Power Supply
Using panel's Port2
DB 15-pin - female
Protocol(s)
Components &
Supported
Network Type
AutomationDirect
EA-2CBL
Modbus (CLICK)
RS-232
K-sequence,
EA-2CBL
Direct NET,
RS-232
Modbus RTU
EA-2CBL
RS-232
K-sequence,
EA-2CBL-1
Direct NET,
RS-232
Modbus RTU
** See Diagram 1
RS-422
** See Diagram 2
Modbus RTU
RS-485
Modbus only
EA-2CBL
RS-232
K-sequence,
EA-2CBL-1
Direct NET,
RS-232
Modbus RTU
** See Diagram 1
RS-422
** See Diagram 2
Modbus RTU
RS-485
Modbus only
EA-2CBL
RS-232
K-sequence,
EA-2CBL-1
Direct NET,
RS-232
Modbus RTU
** See Diagram 1
RS-422
** See Diagram 2
Modbus RTU
RS-485
Modbus only