C-more micro EA1-S6ML Hardware User Manual page 118

Micro-graphic panel - 6 inch
Table of Contents

Advertisement

Chapter 6: PLC Communications
User Constructed Cables – Wiring Diagrams (cont'd)
Diagram 9
To PLC
9-Pin Port
9-pin
D-sub
(male)
1 = do not use
2 = RXD
3 = TXD
4 = DTR
5 = Signal GND
1
6
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
Diagram 10
To PLC
110 CPU 311-xx, 110 CPU 411-xx, 110 CPU 512-xx, 110 CPU 612-xx
9-Pin Port
9-pin
D-sub
(female)
1
1 = do not use
2 = TXD
3 = RXD
4 = do not use
5 = Signal GND
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
6–30
Modicon™ ModBus™, 984 CPU, Quanum 113 CPU
3
TXD
9
6 = DSR
2
RXD
7 = RTS
5
8 = CTS
GND
9 = do not use
4
DTR
6
DSR
7
RTS
8
CTS
AEG Modicon™ Micro Series:
2
6 = do not use
TXD
7 = do not use
3
RXD
8 = do not use
5
9 = do not use
GND
9
®
EA1-MG6-USER-M Hardware User Manual, 1st Ed. Rev C, 09/10
RS-232C
Wiring Diagram
3
RXD
2
TXD
5
1
shield
RS-232C
Wiring Diagram
3
RXD
2
TXD
5
1
shield
User Constructed
To C-more Micro-Graphic
Serial Port2
15-pin
D-sub
8 = do not use
(male)
15 = do not use
7 = do not use
14 = do not use
6 = do not use
15
13 = do not use
5 = Logic GND
12 = do not use
4 = do not use
11 = do not use
3 = RXD (232C)
10 = do not use
2 = TXD (232C)
9 = do not use
1
1 = Frame GND
User Constructed
To C-more Micro-Graphic
Serial Port2
15-pin
D-sub
8 = do not use
15 = do not use
(male)
7 = do not use
14 = do not use
6 = do not use
13 = do not use
15
5 = Logic GND
12 = do not use
4 = do not use
11 = do not use
3 = RXD (232C)
10 = do not use
2 = TXD (232C)
9 = do not use
1
1 = Frame GND

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EA1-S6ML and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ea-mg6-bz2pEa1-s6mlwEa-mg6-bz2

Table of Contents