Omron FINS Protocol – PLC Error Code Table
The following table lists the errors that can be generated by the Omron PLC when using the
FINS protocol.
Note: The following errors can be generated from the designated PLC, are monitored by the C-more Micro-
Graphic panel, and displayed on the panel's screen as a hexadecimal value in panel error code P499, if active.
Please refer to the PLC manufacturer's documentation for additional information.
Panel Error Code
P499 Hex Value
0x0000
Normal Completion.
0x0001
Service Canceled.
0x0101
Local Error: Local node not in network.
0x0102
Local Error: Token Timeout.
0x0103
Local Error: Retries Failed.
0x0104
Local Error: Too many send frames.
0x0105
Local Error: Node address range error.
0x0106
Local Error: Node Address Duplication.
0x0201
Destination Node Error: Destination Node not in network.
0x0202
Destination Node Error: Unit Missing.
0x0203
Destination Node Error: Third Node missing.
0x0204
Destination Node Error: Destination Node busy.
0x0205
Destination Node Error: Response Timeout.
0x0301
Controller Error: Communications Controller Error.
0x0302
Controller Error: CPU Unit Error.
0x0303
Controller Error: Controller Error.
0x0304
Controller Error: Unit number Error.
0x0401
Service Unsupported: Undefined Command.
0x0402
Service Unsupported: Not supported by Model/Version.
0x0501
Routing Table Error: Destination address setting error.
0x0502
Routing Table Error: No routing tables.
0x0503
Routing Table Error: Routing table error.
0x0504
Routing Table Error: Too many delays.
0x1001
Command Format Error: Command too long.
0x1002
Command Format Error: Command too short.
0x1003
Command Format Error: Elements/Data don't match.
0x1004
Command Format Error: Command format error.
0x1005
Command Format Error: Header Error.
0x1101
Parameter Error: Area classification missing.
0x1102
Parameter Error: Access Size Error.
0x1103
Parameter Error: Address range error.
(PLC generated error codes for the Omron FINS protocol continued on the next page.)
®