The SRC Table Directed You Here and the SRC is 1xxx1200

The power system in the system rack is failing.
Attention:
removing or installing regulators R04, R05, or R06.
1. Perform the following:
a. Power off the system.
b. Remove regulator assemblies R01, R02, and R07 through R10 from the
c. Power on the system.
Is SRC 1xxx1200 displayed?
No
Yes
2. Perform the following:
a. Power off the system.
b. Remove one of the blowers from the system rack not previously removed
c. Power on the system.
Is SRC 1xxx1200 displayed?
No
Yes
3. Have you removed all the blowers one at a time?
No
Yes
4. Perform the following:
a. Power off the system.
b. Install the blower that was removed in step 2.
c. Go to step 2.
5. Perform the following:
a. Power off the system.
b. Remove all except one of the bulk power supplies from the system rack.
c. Power on the system.
Is SRC 1xxx1200 displayed?
No
Yes
6. Perform the following:
102
Service Guide
The ac power cable must be disconnected from the system rack before
system rack. Do not remove R04, R05, and R06.
Go to step 15 on page 104.
Go to step 2.
during this procedure.
The blower you removed in this step is failing, replace the blower.
This ends the procedure. Go to "Map 0410: Repair Checkout" in the
Diagnostic Information for Multiple Bus Systems.
Go to step 3.
Go to step 4.
Install all blowers and go to step 5.
Go to step 12 on page 104.
Go to step 6.