Visonic PowerMaster-10 Installer's Manual page 82

Fully supervised wireless alarm control system
Hide thumbs Also See for PowerMaster-10:
Table of Contents

Advertisement

05:CONFIRM ALARM
06:CONFIRM PANIC
07:RPT CNFM ALRM
08:ENTRY DELAY 1
09:ENTRY DELAY 2
Smoke Siren Test
Siren Test: Each siren of the system is automatically activated for 3 seconds (outdoor sirens with low volume). In
addition, the system tests the siren of enrolled smoke sensors.
Using the Installer Code
This section is an update to the PowerMaster-10/30 G2 Installer's Guide – section 4.2.
Option
SIRENS TEST
D-304271 PowerMaster-10/30 G2 Addendum
Define a specific time period that if 2 successive alarms occur, the second alarm will be
considered as a confirmed alarm, (see REPORT CNFRM ALARM below).
Options: 30/45/60 (default)/90 minutes
A confirmed panic alarm is reported if one of the following occurs within the confirmation time:
a) A second panic device is activated.
b) A second panic alarm on the same device is activated.
c) A tamper event is activated (not from the zone / device that initiated the panic alarm).
Options: 4/8/12/20 (default)/24 hours and disabled
Define whether the system will report a confirmed alarm.
enable + bypass (default) - The system will report a confirmed alarm and will bypass all
alarmed open zones when the siren ends or when the confirmation timer expires.
disable - The system will not report a confirmed alarm.
enable - The system will report a confirmed alarm.
Two different entry delays allow the user to enter the protected site (while the system is in the
armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Options: 10/15/30 (ENTRY DELAY 1 default)/45/60 (ENTRY DELAY 2 default) seconds;
3/4 minutes
Instructions
You can test wireless sirens and strobes (including the control panel siren) and sirens of
smoke sensors.
To initiate the siren test press
zone location assigned to the siren that is currently being tested.
First the panel siren sounds for 3 seconds after which the PowerMaster system will
automatically repeat the procedure for the next siren enrolled in the system until all sirens are
tested. You should listen to the sirens sounds and make sure that all sirens sound.
Once all the sirens have been tested, the control panel will now test the sirens of smoke
sensors that are enrolled in the alarm system. The display now reads "Zxx: SMOKE SIREN",
where "Zxx" indicates the zone number of the smoke sensor, and alternates with "<OK> TO
CONTINUE". During this time, the siren of the tested smoke sensor will sound for up to one
minute.
Press
to test the siren of the next smoke sensor.
When the sirens test is complete, the display reads "SIREN TESTS END". Press the
or the
button to confirm the test.
. The display now reads "SIREN N". "N" indicates the
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powermaster-30

Table of Contents