7.7 Restoring Factory Configuration
Introduction
This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.28.
ATTENTION
Restoring the factory configuration overwrites all user-entered configuration
changes. This procedure cannot be undone; it is a one-way process.
Table 7-16 explains how to restore Factory Configuration.
Step
1
Turn off the power to the instrument for at least five seconds.
2
Turn the power back on and simultaneously press the "SETUP" and
keys. This must be done while "TEST DONE" is being displayed.
3
If step 2 was performed correctly, the instrument will now display "UDC"
[Upper] "UPDATE" [Lower].
4
Press the
"RESTORE" [Lower].
5
Press the
"RESTORE" [Lower].
6
Press the
"RESTORE" [Lower].
When the instrument finishes the restore operation, it automatically resets
7
itself and restarts in the product mode. The instrument configuration will
now be the same as it was when the instrument left the factory and all user-
entered configurations since that time have been overwritten.
10/05
Table 7-16 Restoring Factory Configuration
Func
Loop 1/2
Key. The instrument will now display "DIS" [Upper]
key. The instrument will now display "CONFIG" [Upper]
Func
Loop 1/2
Key. The instrument will now display "DOING" [Upper]
UDC3500 Universal Digital Controller Product Manual
What to do
Troubleshooting/Service