Figure 2-9 Hlai Inputs 2 And 4 Connections - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Installation
ATTENTION:
Check Input 2 jumper when
replacing single input with two
HLAI.
0-5V or 1-5V Connections
Input 4 Source
+
Input 2 Source
+
1
The 250 ohm resistors for milliamp inputs are supplied with the controller when those inputs are specified.
These items must be installed prior to start up when the controller is wired. For 0-20 mA applications, the
resistor should be located at the transmitter terminals if Burnout detection is desired.
See Figure 2-11 for Jumper Positions.
32
10
L1
11
L2/N
12
4
13
5
14
6
15
7
16
8
17
9
18

Figure 2-9 HLAI Inputs 2 and 4 Connections

UDC3500 Universal Digital Controller Product Manual
19
28
20
29
+
21
30
+
22
31
23
32
33
24
34
25
26
35
27
36
0-20 or 4-20mA Connections
Transmitter 4
+
31
+
+
32
Transmitter 2
+
33
High Level
Analog Input
Connections
See Below
31
1
250 Ω
32
250 Ω
1
33
+
Power
Supply
+
+
10/05