Honeywell UDC3500 Product Manual page 43

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Input #2
Input #1
Thermocouple
Thermocouple
Use Thermocouple
Use Thermocouple
extension wire only
extension wire only
3
1
3 2
0-10 Volts or –1 to 1 Volts
+
+
1
1
100K
100K
Volt
Volt
2
2
3
1
source
source
100K
100K
3
3
1
Remove the "R" terminal screw and install the C/J Sensor in its place. Connect the tang to the "−" terminal.
This controller does not produce a steady current for burnout detection. For that reason, when a
2
thermocouple is used in parallel with another instrument, it may be desirable to configure the burnout
selection for this controller to "NOFS" and use the burnout current from the other instrument to also drive
this controller. The Failsafe Output must be set to ensure proper operation when the thermocouple fails.
The 250 ohm resistor for milliamp inputs or the voltage divider for 0 to10 Volt or –1 to 1Volt inputs are
3
supplied with the controller when those inputs are specified. These items must be installed prior to start up
when the controller is wired. For 0-20 mA, -1 to 1 Volt and 0-10 Volt applications, the resistor should be
located at the transmitter terminals if Burnout detection is desired.
Splice and tape this junction between the two thermocouples. This junction may be located anywhere
4
between the thermocouples and the instrument terminals, it does not need to be close to the other
thermocouple junctions. Both thermocouples must be of the same type. For the highest accuracy, the
thermocouples should be matched or, preferably, made from the same batch of wire.
The millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at an ambient
5
temperature mean of 450°F / 232°C. Cold Junction Compensation is not required for this input type.
10/05
RTD
RTD
34
22
R
R
23
35
+
+
36
24
Milliamps
Milliamps
34
22
R
R
Xmitter
Xmitter
3
1
+
+
+
+
35
23
250 Ω
250 Ω
Power
Power
24
36
+
+
Supply
Supply
Figure 2-6 Input 1 Connections
UDC3500 Universal Digital Controller Product Manual
Carbon, Oxygen, Millivolt or Volts
except 0 to 10 Volts or –1 to 1 Volts
34
22
R
R
+
+
35
23
+
+
mV or
mV or
Volt
Volt
source
source
36
24
Thermocouple Differential
Thermocouple Differential
Use Thermocouple
Use Thermocouple
extension wire only
extension wire only
34
22
R
R
+
+
23
35
+
+
2
4
24
36
5
+
+
Installation
34
22
R
R
+
+
35
23
36
24
22
34
R
R
23
35
+
+
36
24
29