Function Prompt
Lower Display
10/05
Selections or
Range of Setting
Upper Display
2PV SW
2SP SW
4SP SW
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
Configure the values for:
Gain #3, Rate #3 , Reset #3, Cycle #3 Time
Gain #4, Rate #4, Reset #4, Cycle #4 Time
TWO SETS PV AUTOMATIC SWITCHOVER—
When the process variable is GREATER than the
value set at prompt SW VALUE (Switchover Value),
the controller will use Gain #3, Rate #3, Reset #3,
and Cycle #3 Time. The active PID SET can be read
in the lower display.
When the process variable is LESS than the value
set at prompt SW VALUE, the controller will use
Gain #4, Rate #4, Reset #4, and Cycle #4 Time. The
active PID SET can be read in the lower display.
Other prompts affected: SW VALUE
TWO SETS SP AUTOMATIC SWITCHOVER—
When the setpoint is GREATER than the value set at
prompt SW VALUE (Switchover Value), the
controller will use Gain #3, Rate #3, Reset #3, and
Cycle #3.
When the setpoint is LESS than the value set at
prompt SW VALUE, the controller will use Gain #4,
Rate #4, Reset #4, and Cycle #4.
Other prompts affected: SW VALUE
FOUR SETS SP AUTOMATIC SWITCHOVER—
When the setpoint is GREATER than the value set at
prompt SW VALUE (Switchover Value), the
controller will use Gain, Rate, Reset, and Cycle.
When the setpoint is LESS than the value set at
prompt SW VALUE, the controller will use Gain #2,
Rate #2, Reset #2, and Cycle #2.
Similarly, the controller switches between the other
PID sets based upon the values configured for SW
VAL 2 and SW VAL 3.
ATTENTION Other prompts affected: SW VALUE,
SW VAL 2 and SW VAL 3.