Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Input Algorithm 1
Input A Selection
(used with ID 204
math
calculations)
Input Algorithm 1
Input B Selection
(used with ID 204
math
calculations)
Input Algorithm 1
Input C Selection
(used with ID 204
math
calculations)
Algorithm1 bias
Percent Carbon
Monoxide
Percent Carbon
Monoxide Value
Atmospheric
Pressure
Percent
Hydrogen
352
Register
Address
ID
Hex
Decimal
205
00CD
205
206
00CE
206
207
00CF
207
92
005C
092
203
00CB
203
46
002E
046
24
0018
024
34
0022
034
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop 1 Output
6 = Loop 2 Output
7 = Input Algorithm 1
8 = Input Algorithm 2
INT
R/W
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop 1 Output
6 = Loop 2 Output
7 = Input Algorithm 1
8 = Input Algorithm 2
INT
R/W
0 = None
1 = Input 1
2 = Input 2
3 = Input 3
4 = Input 4
5 = Input 5
6 = Loop 1 Output
7 = Loop 2 Output
8 = Input 1 Algorithm
9 = Input 2 Algorithm
FP
R/W
-999.0 to 9999 in
Engineering Units
INT
R/W
0 = Manual
1 = On Line (via Input 3
only)
FP
R/W
0.02 to 0.350
FP
R/W
590 to 760
FP
R/W
1 to 99 (% H2)
Data Range or