Display; Table 10-30 Set-Up Group - Display - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.21

Display

Table 10-30 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Display.
Parameter
Description
Decimal Point
Location
Decimal Point
Location Loop2
Temperature
Units
Power Frequency
Language
(Displays)
Ratio Input 2 from
Front Panel
ID Number
396
Table 10-30 Set-up Group – Display
Register
Address
ID
Hex
Decimal
155
009B
155
155
019B
411
129
0081
129
166
00A6
166
192
00C0
192
208
00D0
208
41
0029
41
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
0 = None – Fixed
INT
R/W
1 = One – Floating decimal
2 = Two – Floating decimal
3 = Three – Floating
0 = None – Fixed
INT
R/W
1 = One – Floating decimal
2 = Two – Floating decimal
3 = Three – Floating
0 = °F
INT
R/W
1 = °C
2 = None
INT
R/W
0 = 60 Hertz
1 = 50 Hertz
INT
R/W
0 = English
1 = French
2 = German
3 = Spanish
4 = Italian
INT
R/W
0 = Disable
1 = Enable
INT
R/W
0 to 255
Data Range or
point to one
point to two
decimal point to three
point to one
point to two
decimal point to three
10/05

Advertisement

Table of Contents
loading

Table of Contents