Honeywell UDC3500 Product Manual page 229

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Step
Operation
Manual Reset
Function
4
Select Control
Set-up Group
Select PID SETS
5
6
Select PID SETS
Function
Select LSP'S
7
8
Select LSP'S
Function
9
Select SP TRACK
Select SP TRACK
10
Function
Select Tuning
11
Set-up Group
12
Select Manual
Reset Value
13
Configure Manual
Reset Value
Select Algorithm
14
Set-up Group
Select Control
15
Algorithm
16
Select PID A
10/05
Press
PD+MR— PD + Manual Reset
Until you see:
Upper Display = SET
Setup
Setup
Lower Display = CONTROL
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = PID SETS
To select
or
2KEYBD—2 sets, keyboard selectable
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = LSP'S
To select
or
TWO—Two LSP's
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = SP TRACK
To select
or
NONE—No SP Tracking
Until you see:
Setup
Setup
Upper Display = SET
Lower Display = TUNING
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = MAN RSET
To configure:
or
0— Manual Reset Value
A Manual Reset of 0 is for no output bias and requires that
LSP2 = 0 % of the Setpoint Range. If bias is required, set
the Manual Reset value to equal the desired output bias
value.
Until you see:
Setup
Setup
Upper Display = SET
Lower Display = ALGORTHM
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = CONT ALG
To select:
or
PID A— PID A
This is defining the back-up control algorithm.
UDC3500 Universal Digital Controller Product Manual
Monitoring and Operating the Controller
Result
215

Advertisement

Table of Contents
loading

Table of Contents